52
ACS 300 User’s Manual
Chapter 7 - Drive Parameters
OUTPUT I
Calculated motor phase current. Accuracy ±10%. Includes cable
losses.
Note! This display is not for accurate measurement.
COPY
Copy is used to transfer all parameter settings from one ACS 300
to another.
EXIT
Copy function not selected.
READ
Reads all parameter values from the ACS 300 to the control
panel memory.
WRITE
Copies all parameter values from the control panel memory to
the ACS 300.
SET FACTORY DEF
If you select SET FACTORY DEF and press the
key, all the
parameters will be reset to the factory settings.
MIN FREQ
MAX FREQ
Reference input minimum and maximum frequency.
Note! MIN can be set higher than MAX for analogue input signal
inverse operation.
ACC TIME 1
DEC TIME 1
ACC TIME 2
DEC TIME 2
These times correspond to the time required for the output
frequency to change from MIN FREQ to MAX FREQ and vice
versa. Regardless of the settings, the maximum theoretical
frequency changing speed is 120 Hz/0.1 s and the minimum
100 Hz/1800 s. The time required for acceleration from zero to
minimum frequency depends on ACC 1.
When the selected I/O mode is Standard or Alternate, DI5 selects
ACC/DEC 1 or 2. 0 V = ramp 1 and +24 V = ramp 2. Refer to
page 27 for a detailed explanation of I/O modes.
Summary of Contents for ACS 300
Page 14: ...xiv ACS 300 User s Manual Table of Contents ...
Page 24: ...10 ACS 300 User s Manual Chapter 1 Overview of This Manual ...
Page 28: ...14 ACS 300 User s Manual Chapter 2 Mechanical Installation ...
Page 50: ...36 ACS 300 User s Manual Chapter 4 Control Connections ...
Page 60: ...46 ACS 300 User s Manual Chapter 6 Control and Parameter Logic ...