Chapter 9 - Technical Data
Protection
Accessories
Short-circuit overcurrent trip limit
3.5 x I
N
Output current regulation limit
0.5 -1.5 x I
N
Overvoltage trip limit
1.35 x U
240
, 1.3 x U
480
Undervoltage trip limit
0.65 x U
N
Overtemperature limit
90
°
C, heatsink
Auxiliary voltage
short-circuit protected
Earth fault protection
protects only the ACS 300 when an
earth fault occurs at motor output
Control Panel
IP 65 set
for Panel
Braking resistor
R0, R1, R2
External braking chopper
R2
Line Choke
R0, R1 (R2 standard)
RFI Filter
R0 Type S-492-10, (R1,R2 standard)
Output choke
RS 232 adapter
Fieldbus adapters