ACS 300 User’s Manual
35
Chapter 4 - Control Connections
Figure 4-6 Motor Potentiometer switch S1 selection.
Motor
Potentiometer 2
Switch S1 is in the same position as in Motor potentiometer
selection. Parameter PARAM SET has value 2.
Table 4-15 Motor Potentiometer 2 selection.
The ACS 300 accelerates/decelerates using Page 1/ Page 4
parameters ACC 1/ DEC 1 when changing rotation direction.
Acceleration from 0 Hz to MIN FREQ is also done with ramp 1.
Digital input
Function
Notes
DI1
Start
C24 V DC to Start
DI2
Reverse
C24 V DC to reverse
DI3
Increment fr.
C24 V DC to increment fr. (ramp 2)
DI4
Decrement fr.
C24 V DC to decrement fr. (ramp 2)
DI5
Parameter set selection
0 V= set 1 and +24 V= set 2
OFF
ON
0
1
Motor potentiometer
Summary of Contents for ACS 300
Page 14: ...xiv ACS 300 User s Manual Table of Contents ...
Page 24: ...10 ACS 300 User s Manual Chapter 1 Overview of This Manual ...
Page 28: ...14 ACS 300 User s Manual Chapter 2 Mechanical Installation ...
Page 50: ...36 ACS 300 User s Manual Chapter 4 Control Connections ...
Page 60: ...46 ACS 300 User s Manual Chapter 6 Control and Parameter Logic ...