ACS 300 User’s Manual
Chapter 8 - Fault Tracing
(6) PANEL COM ERR
Control Panel was removed
when control was in Local mode.
Due to safety reasons, the drive
stops in this fault condition.
•
Attach the Control Panel and
reset the fault, then change to
Remote mode and remove
Panel.
•
Use remote (wired) controls to
reset the fault, then start and
run with remote controls
•
There might be a loose contact.
Check the panel connection.
(10) BUS COMM FLT
Bus communication error
•
Check bus connections
(7) UNIT FAULT
ACS 300 heatsink temperature
too high.
CHECK:
•
Heatsink dissipation
•
Dust and dirt
•
Air flow
•
Fan
•
Ambient temperature
•
Reduce switching frequency.
•
Check load current
Earth faults or short circuits.
CHECK:
•
Terminals
•
Motor
•
Cables
With frame size R2 high load
inertia / short ramp
CHECK:
•
Ramps times
•
Remove mechanical problems
•
Dimensioning
(8) UNIT FAULT
Inverter control unsuccessful.
•
Switch power off.
•
If fault persists, contact your
nearest ACS 300 supplier.
Fault indication
Possible cause
Remedy