Note!
Alarms (*) will not cause relay output RO1 (RO2) to activate when the relay output is
configured to indicate alarm condition in general. (Parameter 1401
RELAY OUTPUT
1 (1402
RELAY OUTPUT
2) has value 5 (
ALARM
) or 13 (
FLT
/
ALARM
)).
Note!
Alarms (**) will be shown only if parameter 1608
DISPLAY
ALARMS
is set to 1 (
YES
)
25
Reserved.
26 **
OUTPUT
OVERLOAD
Inverter overload condition. The ACS 160 output current exceeds the ratings
given in Reference Section
.
27 *
AUTOMATIC
RESET
ACS 160 is about to perform automatic fault reset operation. As a result, the
drive may start after the reset operation. Refer to parameter group 31
AUTOMATIC RESET.
28 *
PID
SLEEP
PID sleep function is active. The drive may accelerate when PID sleep function
is deactivated. Refer to parameters 4018
SLEEP
SELECTION
, 4013
PID
SLEEP
DELAY
, 4014
PID
SLEEP
LEVEL
and 4015
WAKE
-
UP
LEVEL
.
29 Reserved.
30
Reserved.
31
BR
RES
OVERLOAD
Brake resistor is nearly overloaded. Refer to brake resistor instructions.
Alarm
Code
Name
Description
Summary of Contents for ACS 160
Page 2: ......
Page 4: ......
Page 10: ...viii ACS 160 User s Manual ...
Page 12: ...2 ACS 160 User s Manual ...
Page 32: ...22 ACS 160 User s Manual ...
Page 42: ...32 ACS 160 User s Manual ...
Page 56: ...46 ACS 160 User s Manual ...
Page 116: ...106 ACS 160 User s Manual ...
Page 122: ...112 ACS 160 User s Manual ...
Page 126: ...116 ACS 160 User s Manual ...
Page 136: ...126 ACS 160 User s Manual ...
Page 137: ......