110
ACS 160 User’s Manual
Table 9 Faults.
Fault Code
Name
Description
1
OVERCURRENT
Output current is excessive.
•
Motor load may be too high
•
Acceleration time may be too short (parameters 2201
ACCELER
TIME
1 and 2203
ACCELER
TIME
2).
•
Motor or motor cable is faulty or connected wrong.
2
DC
OVERVOLTAGE
Intermediate circuit DC voltage is excessive.
•
Check mains for static or transient overvoltages
•
Deceleration time may be too short (parameters 2202
DECELER
TIME
1 and 2204
DECELER
TIME
2)
•
Brake chopper (if present) may be underdimensioned
3
ACS
160
OVERTEMP
ACS 160 heat sink temperature is excessive. Temperature trip limit is
105 °C.
•
Check air flow and fan operation.
•
Check motor power against unit power.
4 **
SHORT
CIRCUIT
Fault current. Possible reasons for this fault are:
•
There is a short-circuit in the motor cable(s) or motor
•
Supply disturbances
5
OUTPUT
OVERLOAD
Inverter overload condition. The ACS 160 output current exceeds the
ratings given in Reference Section
.
6
DC
UNDERVOLTAGE
Intermediate circuit DC voltage is not sufficient.
•
Mains phase may be missing
•
Fuse may be blown
7
ANALOGUE
INPUT
1
Analogue input 1 loss. Analogue input value is less than
MINIMUM
AI
1
(1301). See also parameter 3001
AI
<
MIN FUNCTION
.
8
ANALOGUE
INPUT
2
Analogue input 2 loss. Analogue input value is less than
MINIMUM
AI
2
(1306). See also parameter 3001
AI
<
MIN FUNCTION
.
9
MOTOR
OVERTEMP
Motor overtemperature condition as estimated by the ACS 160. Refer to
parameters 3004 – 3008.
10
PANEL
LOSS
Panel communication loss. Control panel is disconnected when the
drive is receiving start, stop and direction commands from the panel.
- Drive is in local control mode (LOC is shown in the control panel
display), or
- Drive is in remote control mode (REM is shown) and is parameterised
to accept start/stop, direction or reference from the panel. Refer to
parameters in groups 10 COMMAND INPUTS and 11 REFERENCE
SELECT.
See also parameter 3002
PANEL
LOSS
.
11
PARAMETERING
Parameter values are inconsistent:
•
MINIMUM
AI
1 >
MAXIMUM
AI
1 (parameters 1301, 1302)
•
MINIMUM
AI
2 >
MAXIMUM
AI
2 (parameters 1304, 1305)
•
MINIMUM
FREQ
>
MAXIMUM
FREQ
(parameters 2007, 2008)
12
MOTOR
STALL
Motor stall. This may be caused by excessive load or insufficient motor
power. Refer to parameters 3009 – 3012.
13
SERIAL
COMM
LOSS
Serial communication through Standard Modbus Channel is lost.
•
Check connections between external control system and the
ACS 160.
•
Refer to parameters 5204
COMM
FAULT
TIME
and 5205
COMM
FAULT
FUNC
.
14
EXTERNAL
FAULT
SIGNAL
External fault is active. See parameter 3003
EXTERNAL
FAULT
.
15 **
OUTPUT
EARTH
FAULT
Earth fault. The load on the incoming mains system is out of balance.
•
There may be a fault in the motor or motor cable.
•
Motor cable may be too long.
16 **
DC
BUS
RIPPLE
•
Ripple voltages on the DC bus are too large.
•
Mains phase may be missing
•
Fuse may be blown
Summary of Contents for ACS 160
Page 2: ......
Page 4: ......
Page 10: ...viii ACS 160 User s Manual ...
Page 12: ...2 ACS 160 User s Manual ...
Page 32: ...22 ACS 160 User s Manual ...
Page 42: ...32 ACS 160 User s Manual ...
Page 56: ...46 ACS 160 User s Manual ...
Page 116: ...106 ACS 160 User s Manual ...
Page 122: ...112 ACS 160 User s Manual ...
Page 126: ...116 ACS 160 User s Manual ...
Page 136: ...126 ACS 160 User s Manual ...
Page 137: ......