ACS 160 User’s Manual
111
Note!
Faults (**) are indicated by a red blinking LED and are reset by turning the power off for a
while.
17
UNDERLOAD
Motor load is too low. Check for a problem in the driven equipment.
Refer to parameters 3013 – 3015.
18
Reserved
19
Reserved.
20 **
AI
OUT
OF
RANGE
Analogue input out of range. Check AI level.
21 - 29 **
HARDWARE
ERROR
Hardware error. Contact supplier.
30
BR
RES
OVERLOAD
Brake resistor is overloaded. Refer to parameter 2005
OVERVOLT
CTRL
.
31
ENCODER
FAULT
Positioning macro is used, but the drive is not receiving pulses. Check
the encoder and its connections.
Full display blinking
Serial link failure. Bad connection between the control panel and the
ACS 160.