68
ACS 160 User’s Manual
Group 15: Analogue Output
Analogue output is used to output the value of any parameter of the Operating Data group (Group 1)
as a current signal. Output current minimum and maximum values are configurable, as are the
allowed minimum and maximum values for the observed parameter.
If analogue output content maximum value (parameter 1503) is set to less than minimum value
(parameter 1502), output current is inversely proportional to the value of the observed parameter.
Figure 9 Analogue output scaling.
Code Description
1501
AO CONTENT
Content for analogue output. Number of any parameter of the Operating Data group (Group 01).
1502
AO CONTENT MIN
Analogue output content minimum. Display depends on parameter 1501.
1503
AO CONTENT MAX
Analogue output content maximum. Display depends on parameter 1501.
1504
MINIMUM AO
Minimum output current.
1505
MAXIMUM AO
Maximum output current.
1506
AO FILTER
Filter time constant for AO.
AO (mA)
AO content
1504
1502
1503
AO (mA)
AO content
1505
1504
1503
1502
1505