48
ACS 160 User’s Manual
0122
AO
0 - 20 mA
0.1 mA
-
22
0124
ACTUAL
VALUE
1
0 - 100 %
0.1 %
-
24
0125
ACTUAL
VALUE
2
0 - 100 %
0.1 %
-
25
0126
CONTROL
DEV
-100 - 100 %
0.1 %
-
26
0127
PID
ACT
VALUE
-100 - 100 %
0.1 %
27
0128
LAST
FAULT
0 - 26
1
28
0129
PREVIOUS
FAULT
0 - 26
1
29
0130
OLDEST
FAULT
0 - 26
1
30
0131
SER
LINK
DATA
1
0 - 255
1
31
0132
SER
LINK
DATA
2
0 - 255
1
32
0133
SER
LINK
DATA
3
0 - 255
1
33
0134
PROCESS
VAR
1
-
-
34
0135
PROCESS
VAR
2
-
-
35
0136
RUN
TIME
0.00 - 99.99 kh
0.01 kh
36
0137
MWh
COUNTER
0 - 9999 MWh
1 MWh
37
Group 10
COMMAND INPUTS
1001
EXT
1
COMMANDS
0 - 10
1
2 / 4
101
ü ü
1002
EXT
2
COMMANDS
0 - 10
1
0
102
ü ü
1003
DIRECTION
1 - 3
1
3
103
ü ü
Group 11
REFERENCE SELECT
1101
KEYPAD
REF
SEL
1 - 2
1
1 (
REF
1 (Hz))
126
1102
EXT
1/
EXT
2
SEL
1 - 8
1
6
127
ü ü
1103
EXT
REF
1
SELECT
0 - 13
1
1
128
ü ü
1104
EXT
REF
1
MIN
0 - 250 Hz
1 Hz
0 Hz
129
1105
EXT
REF
1
MAX
0 - 250 Hz
1 Hz
50 Hz / 60 Hz
130
1106
EXT
REF
2
SELECT
0 - 13
1
0
131
ü ü
1107
EXT
REF
2
MIN
0 - 100 %
1 %
0 %
132
1108
EXT
REF
2
MAX
0 - 500 %
1 %
100 %
133
1115
REF
STEP
SEL
0 - 2
1
0
140
1117
REF
STEP
MODE
0 - 1
1
1
142
1118
REF
STEP
UP
0 - 250 Hz
0 - 250 %
0.1 Hz
0.1 %
0
0
143
1119
REF
STEP
DOWN
0 - 250 Hz
0 - 250 %
0.1 Hz
0.1 %
0
0
144
1120
STEP
DLY
ON
0 - 25.0 s
0.1 s
0
145
1121
STEP
DLY
OFF
0 - 25.0 s
0.1 s
0
146
Group 12
CONSTANT SPEEDS
1201
CONST
SPEED
SEL
0 - 10
1
3 / 0
151
ü ü
1202
CONST SPEED
1
0 - 250 Hz
0.1 Hz
5 Hz
152
1203
CONST SPEED
2
0 - 250 Hz
0.1 Hz
10 Hz
153
Code Name
Range
Resolution
Default /
US Default
Profibus
par. num User
S
M
Summary of Contents for ACS 160
Page 2: ......
Page 4: ......
Page 10: ...viii ACS 160 User s Manual ...
Page 12: ...2 ACS 160 User s Manual ...
Page 32: ...22 ACS 160 User s Manual ...
Page 42: ...32 ACS 160 User s Manual ...
Page 56: ...46 ACS 160 User s Manual ...
Page 116: ...106 ACS 160 User s Manual ...
Page 122: ...112 ACS 160 User s Manual ...
Page 126: ...116 ACS 160 User s Manual ...
Page 136: ...126 ACS 160 User s Manual ...
Page 137: ......