![ABB ACQ580-34 Hardware Manual Download Page 43](http://html.mh-extra.com/html/abb/acq580-34/acq580-34_hardware-manual_2546043.webp)
Insulation supports
Strength class
Max. torque
Size
8.8
5 N·m (44 lbf·in)
M6
8.8
9 N·m (6.6 lbf·ft)
M8
8.8
18 N·m (13.3 lbf·ft)
M10
8.8
31 N·m (23 lbf·ft)
M12
Cable lugs
Strength class
Max. torque
Size
8.8
15 N·m (11 lbf·ft)
M8
8.8
32 N·m (23.5 lbf·ft)
M10
8.8
50 N·m (37 lbf·ft)
M12
Cooling and degrees of protection
■
Planning the cooling
When you plan the cooling of the cabinet:
• make sure that the ventilation of the installation site is sufficient so that the cooling air
flow and ambient temperature requirements of the module are met (see the hardware
manual)
• leave enough free space around the components to ensure sufficient cooling. Observe
the minimum clearances given for each component. For the module specific free space
requirements, see the respective hardware and cabinet installation manuals.
■
Air-cooled drive systems
Air inlets and outlets
Equip the air inlets and outlets with gratings that:
• are large enough to allow sufficient air flow in and out of the cabinet (critical for correct
cooling of the module)
• guide the air flow
• protect against contact
• prevent water splashes from entering the cabinet
• ensure adequate protection against flames or pressure blast originating from inside the
cabinet in case of arc flash or similar failure.
The drawing below shows two typical cabinet cooling solutions. The air inlet is at the bottom
of the cabinet. The outlet is on the roof or on the upper part of the door if room height is
limited.
Generic cabinet planning instructions 43
Summary of Contents for ACQ580-34
Page 1: ... ABB DRIVES FOR WATER ACQ580 34 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 14: ...14 ...
Page 24: ...24 ...
Page 50: ...50 ...
Page 60: ...60 ...
Page 70: ...70 ...
Page 94: ...94 ...
Page 110: ...110 ...
Page 122: ...122 ...
Page 132: ...Dimension drawing 132 External control unit option P906 ...
Page 140: ...140 ...
Page 144: ...144 ...
Page 164: ...164 ...
Page 184: ...Standard configuration E208 and E210 included 184 Dimension drawings ...
Page 185: ...Drive module with option B051 Dimension drawings 185 ...
Page 186: ...Drive module with options B051 H370 186 Dimension drawings ...
Page 187: ...LCL filter module Dimension drawings 187 ...
Page 190: ...190 ...
Page 208: ... Declaration of conformity 208 The Safe torque off function ...
Page 214: ...214 ...
Page 226: ...226 ...