Typical motor power in light-duty use
P
Ld
Continuous rms output current allowing 50% overload for 1 minute every 10 minutes when parameter
97.02 Minimum switching frequency
is set to 2 kHz or less.
I
Hd
Typical motor power in heavy-duty use
P
Hd
Note:
To achieve the rated motor power given in the table, the rated current of the drive must be higher than
or equal to the rated motor current. The power ratings apply to most IEC 34 motors at the nominal voltage of
the drive.
ABB recommends to select the drive, motor and gear combination for the required motion profile with the
DriveSize dimensioning tool available from ABB.
■
When is derating necessary
Derate the continuous output current of the drive if
• ambient temperature e40 °C (+104 °F) or
• drive is installed higher than 1000 m (3280 ft) above sea level
• the minimum requirements of motor cable length are not met (see
).
Note:
The final derating factor is a multiplication of all applicable derating factors.
■
Surrounding air temperature derating
In the temperature range +40…55 °C (+104…131 °F), the rated output current is derated
by 1% for every added 1 °C (1.8 °F) as follows. Calculate the output current by multiplying
the current given in the rating table by the derating factor.
T
1.00
0.90
+40 °C
+104 °F
+50 °C
+122 °F
k
+55 °C
+131 °F
0.80
-15 °C
+5°F
…
0.85
0.95
■
Altitude derating
At altitudes from 1000 to 4000 m (3300 to 13123 ft) above sea level, the derating is 1% for
every 100 m (328 ft). If ambient temperature is below +40 °C (+104 °F), the derating can
be reduced by 1.5% for every 1 °C reduction in temperature. For a more accurate derating,
use the DriveSize PC tool. A few altitude derating curves are shown below.
Technical data 167
Summary of Contents for ACQ580-34
Page 1: ... ABB DRIVES FOR WATER ACQ580 34 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 14: ...14 ...
Page 24: ...24 ...
Page 50: ...50 ...
Page 60: ...60 ...
Page 70: ...70 ...
Page 94: ...94 ...
Page 110: ...110 ...
Page 122: ...122 ...
Page 132: ...Dimension drawing 132 External control unit option P906 ...
Page 140: ...140 ...
Page 144: ...144 ...
Page 164: ...164 ...
Page 184: ...Standard configuration E208 and E210 included 184 Dimension drawings ...
Page 185: ...Drive module with option B051 Dimension drawings 185 ...
Page 186: ...Drive module with options B051 H370 186 Dimension drawings ...
Page 187: ...LCL filter module Dimension drawings 187 ...
Page 190: ...190 ...
Page 208: ... Declaration of conformity 208 The Safe torque off function ...
Page 214: ...214 ...
Page 226: ...226 ...