Safety data
The safety data for the Safe torque off function is given below.
Note:
The safety data is calculated for redundant use, and does not apply if both STO
channels are not used.
T
M
(a)
CCF
HFT
SC
Cat.
DC
(%)
MTTF
D
(a)
PFD
avg
(T
1
= 5 a)
PFD
avg
(T
1
= 2 a)
PFH
(T
1
= 20 a)
(1/h)
SFF
(%)
PL
SIL/
SILCL
Frame size
20
80
1
3
3
≥90
16398
9.08E-05
3.63E-05
4.14E-09
99.61
e
3
R11
3AXD10000410558 F
• The following temperature profile is used in safety value calculations:
• 670 on/off cycles per year with Δ
T
= 71.66 °C
• 1340 on/off cycles per year with Δ
T
= 61.66 °C
• 30 on/off cycles per year with Δ
T
= 10.0 °C
• 32 °C board temperature at 2.0% of time
• 60 °C board temperature at 1.5% of time
• 85 °C board temperature at 2.3% of time.
• The STO is a type A safety component as defined in IEC 61508-2.
• Relevant failure modes:
• The STO trips spuriously (safe failure)
• The STO does not activate when requested
• A fault exclusion on the failure mode “short circuit on printed circuit board” has been
made (EN 13849-2, table D.5). The analysis is based on an assumption that one
failure occurs at one time. No accumulated failures have been analyzed.
• STO response times:
• STO reaction time (shortest detectable break): 1 ms
• STO response time: 2 ms (typical), 30 ms (maximum)
• Fault detection time: Channels in different states for longer than 200 ms
• Fault reaction time: Fault detection time + 10 ms
• Indication delays:
• STO fault indication (parameter
31.22
) delay: < 500 ms
• STO warning indication (parameter
31.22
) delay: < 1000 ms
■
Abbreviations
Description
Reference
Abbr.
Classification of the safety-related parts of a control system in respect
of their resistance to faults and their subsequent behavior in the fault
condition, and which is achieved by the structural arrangement of the
parts, fault detection and/or by their reliability. The categories are: B,
1, 2, 3 and 4.
EN ISO 13849-1
Cat.
Common cause failure (%)
EN ISO 13849-1
CCF
206 The Safe torque off function
Summary of Contents for ACQ580-34
Page 1: ... ABB DRIVES FOR WATER ACQ580 34 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 14: ...14 ...
Page 24: ...24 ...
Page 50: ...50 ...
Page 60: ...60 ...
Page 70: ...70 ...
Page 94: ...94 ...
Page 110: ...110 ...
Page 122: ...122 ...
Page 132: ...Dimension drawing 132 External control unit option P906 ...
Page 140: ...140 ...
Page 144: ...144 ...
Page 164: ...164 ...
Page 184: ...Standard configuration E208 and E210 included 184 Dimension drawings ...
Page 185: ...Drive module with option B051 Dimension drawings 185 ...
Page 186: ...Drive module with options B051 H370 186 Dimension drawings ...
Page 187: ...LCL filter module Dimension drawings 187 ...
Page 190: ...190 ...
Page 208: ... Declaration of conformity 208 The Safe torque off function ...
Page 214: ...214 ...
Page 226: ...226 ...