Default I/O connection diagram
The default control connections for the Water default are shown below.
500 ohm
Max.
1…10 kohm
X1
1
SCR
Reference voltage and analog inputs and outputs
2
AI1
Signal cable shield (screen)
3
AGND
Output frequency/speed reference
: 0…10 V
1)
4
+10V
Analog input circuit common
5
AI2
Reference voltage 10 V DC
6
Actual feedback:
0…10 V
AGND
7
AO1
8
AO2
Analog input circuit common
Output frequency:
0…10 V
9
AGND
Output current:
0…20 mA
Analog output circuit common
10
+24V
X2 & X3
Aux. voltage output and programmable digital inputs
11
DGND
Aux. voltage 24 V DC, max. 250 mA
2)
12
DCOM
Aux. voltage output common
13
DI1
Digital input common for all
14
DI2
Stop (0) / Start (1)
15
DI3
Not configured
16
DI4
Constant frequency/speed selection
3)
17
Not configured
DI5
18
Not configured
DI6
X6, X7, X8
Not configured
19
RO1C
Relay outputs
20
RO1A
21
RO1B
Ready run
250 V AC / 30 V DC
2 A
22
RO2C
23
RO2A
24
RO2B
Running
250 V AC / 30 V DC
2 A
25
RO3C
26
RO3A
27
RO3B
X5
Fault (-1)
250 V AC / 30 V DC
2 A
29
B+
Embedded fieldbus
30
A-
31
DGND
S4
TERM
Embedded fieldbus, EFB (EIA-485)
S5
BIAS
Termination switch
X4
Bias resistors switch
34
Safe torque off
OUT1
35
OUT2
36
SGND
37
IN1
38
IN2
X10
40
24 V AC/DC
41
Safe torque off. Factory connection. Both
circuits must be closed for the drive to start. See
chapter
Safe torque off function
24 V AC/DC+ in
24 V AC/DC- in
Ext. 24V AC/DC input to power up the control unit
when the main supply is disconnected.
7)
4)
6)
4) 4)
5)
1)
Total load capacity of the Auxiliary voltage 24V (X2:10) is 6.0 W (250 mA /
24 V DC).
Control unit 141
Summary of Contents for ACQ580-07
Page 1: ... ABB DRIVES FOR WATER ACQ580 07 Hardware manual ...
Page 2: ......
Page 4: ......
Page 8: ...4 Update notice ...
Page 20: ...16 ...
Page 26: ...Measuring points of frames R6 to R9 are shown below PE L1 L2 L3 22 Safety instructions ...
Page 32: ...28 ...
Page 38: ...34 ...
Page 66: ...62 ...
Page 69: ...Mechanical installation 65 ...
Page 73: ... Mechanical installation 69 ...
Page 75: ...Declaration of Conformity Mechanical installation 71 ...
Page 108: ...104 ...
Page 133: ...Electrical installation 129 ...
Page 142: ...138 ...
Page 156: ...152 ...
Page 162: ...158 ...
Page 171: ...Maintenance 167 ...
Page 177: ...3 4 Maintenance 173 ...
Page 184: ...14 13 15 16 17 Remove the flange 180 Maintenance ...
Page 187: ...3 4 5 6 Remove the mounting plate Maintenance 183 ...
Page 189: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 185 ...
Page 193: ...4 5 3 6 Remove the mounting plate Maintenance 189 ...
Page 195: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 191 ...
Page 218: ...Frame R6 Input and motor cable terminal dimensions option F289 DET A 214 Technical data ...
Page 233: ...Frame R9 Input and motor cable terminal dimensions option F289 Technical data 229 ...
Page 257: ...13 Dimension drawings Example dimension drawings are shown below Dimension drawings 253 ...
Page 258: ...Frames R6 and R7 IP21 UL Type 1 254 Dimension drawings ...
Page 259: ...Frames R6 and R7 B054 IP42 UL Type 1 Filtered Dimension drawings 255 ...
Page 260: ...Frames R6 and R7 B055 IP54 UL Type 12 256 Dimension drawings ...
Page 261: ...Frames R6 and R7 H351 and H353 top entry and exit Dimension drawings 257 ...
Page 262: ...Frames R6 and R7 F289 258 Dimension drawings ...
Page 263: ...Frames R6 and R7 F289 H351 H353 Dimension drawings 259 ...
Page 264: ...Frames R8 and R9 IP21 UL Type 1 260 Dimension drawings ...
Page 265: ...Frames R8 and R9 B054 IP42 UL Type 1 Filtered Dimension drawings 261 ...
Page 266: ...Frames R8 and R9 B055 IP54 UL Type 12 262 Dimension drawings ...
Page 267: ...Frames R8 and R9 H351 and H353 top entry and exit Dimension drawings 263 ...
Page 268: ...Frames R8 and R9 F289 264 Dimension drawings ...
Page 269: ...Frames R8 and R9 F289 H351 H353 Dimension drawings 265 ...
Page 295: ... Declaration of conformity The Safe torque off function 291 ...
Page 296: ...292 ...
Page 302: ...298 ...
Page 309: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 305 ...
Page 310: ...306 ...
Page 316: ...312 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...
Page 322: ...318 ...