ACH580-01 Installation
0012
Motor too large for
advanced standstill ID
run.
Check that the motor and drive sizes
are compatible.
Contact your local ABB
representative.
0013
(Asynchronous motors
only)
Motor data error.
Check that the motor nominal value
settings in the drive are the same as
in the motor nameplate.
Contact your local ABB
representative.
FF63
STO diagnostics failure.
SW internal
malfunction.
Reboot the control unit (using
parameter
96.08 Control board boot
)
or by cycling power.
FF81
FB A force trip
A fault trip command
has been received
through fieldbus
adapter A.
Check the fault information provided
by the PLC.
FF8E
EFB force trip
A fault trip command
has been received
through the embedded
fieldbus interface.
Check the fault information provided
by the PLC.
Code
(hex)
Fault / Aux. code
Cause
What to do