26
ACH580 Installation, Operation and Maintenance Manual
ACH580-01 Installation
500…600 volt, fuse recommendations
ACH580-01-
Input
current
A
UL
Maximum
current
Voltage rating
Bussmannn type
1
UL class
A
V
3-phase
U
N
= 575 V
02A7-6
2.7
15
600
KTK-R-15 or JJS-15
Class CC or T
03A9-6
3.9
15
600
KTK-R-15 or JJS-15
Class CC or T
06A1-6
6.1
15
600
KTK-R-15 or JJS-15
Class CC or T
09A0-6
9
15
600
KTK-R-15 or JJS-15
Class CC or T
011A-6
11
15
600
KTK-R-15 or JJS-15
Class CC or T
017A-6
17
30
600
KTK-R-30 or JJS-30
Class CC or T
022A-6
22
40
600
JJS-40
Class T
027A-6
27
40
600
JJS-40
Class T
032A-6
32
40
600
JJS-40
Class T
041A-6
41
100
600
JJS-100
Class T
052A-6
52
100
600
JJS-100
Class T
062A-6
62
100
600
JJS-100
Class T
077A-6
77
100
600
JJS-100
Class T
099A-6
99
150
600
JJS-150
Class T
125A-6
125
200
600
JJS-200
Class T
144A-6
144
250
600
JJS-250
Class T
180A-6
180
300
600
JJS-300
Class T
242A-6
242
400
600
JJS-400
Class T
271A-6
271
400
600
JJS-400
Class T
1) ABB does not require Bussmann brand fuses. Fuses which meet the appropriate UL class type,
current rating, and are rated at 600V, 200 kA may be used.