![background image](http://html1.mh-extra.com/html/abb/ach580-series/ach580-series_installation-operation-and-maintenance-manual_3357302118.webp)
118
ACH580 Installation, Operation and Maintenance Manual
ACH580 E-Clipse Bypass
Bypass control
The bypass control panel features:
Ready (Power On) Indication
The
Ready (Power On) indication
is provided by the bypass control panel. The
bypass control panel display will be illuminated and text will be displayed when the
disconnect switch or circuit breaker is closed and control power is applied to the
bypass.
Enabled
LED
The
Enabled LED
is illuminated green under the following conditions:
• Both the Start Interlock(s) and Run Permissive contacts are closed.
• The Start Interlock contact(s) are closed with no Start command present.
The Enabled LED flashes green if the Run Permissive contact is open, the Safety
Interlock contact(s) are closed, and Start command is present.
The Enabled LED is illuminated red when the Start Interlock contact(s) are open.
Motor Run LED
The
Motor Run LED
is illuminated green when the motor is running in either bypass
mode or in drive mode. The Motor Run LED flashes green to indicate the system has
been placed in an Override condition.
Bypass Faulted LED
The
Bypass Faulted LED
is illuminated or flashes red when the motor or bypass
protection functions have shut down the bypass. The specific nature of the fault is
indicated on the bypass control display. Refer to the
section of this
manual for more details.
E-CLIPSE BYPASS CONTROL
ESC
ENTER
AUTO
OFF/RESET
HAND
DRIVE
BYPASS
ENABLED
SELECTED
FAULTED
MOTOR RUN
Down
Enabled LED
Drive and Bypass
Selected/Faulted LEDs
Drive/Bypass Select Keys
Motor Run LED
OFF/Reset Key
ON/Hand Key
Enter
Up
LCD Display
Auto Key
Escape
“Ready Indication”
(Display Illuminated)