72
ACH580 Installation, Operation and Maintenance Manual
ACH580-01 Installation
5693
Measurement circuit DFF
Measurement circuit
fault.
Contact your local ABB
representative.
5696
PU state feedback
State feedback from
output phases does not
match control signals.
Contact your local ABB
representative.
5697
Charging feedback
Charging feedback
signal missing.
Check the feedback signal coming
from the charging system.
5698
Unknown PU fault
The power unit logic
has generated a fault
which is not known by
the software.
Check the logic and software
compatibility.
6181
FPGA version
incompatible
Firmware and FPGA
versions are
incompatible.
Reboot the control unit (using
parameter
96.08 Control board boot
)
or by cycling power. If the problem
persists, contact your local ABB
representative.
6306
FBA A mapping file
Fieldbus adapter A
mapping file read error.
Contact your local ABB
representative.
6481
Task overload
Internal fault.
Reboot the control unit (using
parameter
96.08 Control board boot
)
or by cycling power. If the problem
persists, contact your local ABB
representative.
6487
Stack overflow
Internal fault.
Reboot the control unit (using
parameter
96.08 Control board boot
)
or by cycling power. If the problem
persists, contact your local ABB
representative.
64A1
Internal file load
File read error.
Reboot the control unit (using
parameter
96.08 Control board boot
)
or by cycling power. If the problem
persists, contact your local ABB
representative
64A4
Rating ID fault
Rating ID load error.
Contact your local ABB
representative.
64A6
Adaptive program
Error running the
adaptive program.
Check the auxiliary code (format
XXYY ZZZZ).
“XX” specifies the number of the state
(00=base program) and “YY” specifies
the number of the function block
(0000=generic error).
“ZZZZ” indicates the problem.
000A
Program corrupted or
block non-existent
Restore the template program or
download the program to the drive.
000C
Required block input
missing
Check the inputs of the block.
000E
Program corrupted or
block non-existent
Restore the template program or
download the program to the drive.
0011
Program too large.
Remove blocks until the error stops.
0012
Program is empty.
Correct the program and download it
to the drive.
Code
(hex)
Fault / Aux. code
Cause
What to do