40
ACH580 Installation, Operation and Maintenance Manual
ACH580-01 Installation
Default control connections for the PID control, single motor
Terminal sizes:
1. R1…R5: 24…14 AWG (0.2…2.5 mm
2
): Ter24V, DGND, DCOM, B+, A-, DGND, Ext. 24V
2. 26…16 AWG (0.14…1.5 mm
2
): Terminals DI, AI, AO, AGND, RO, STO
3. R6…R9: 26...14 AWG (0.14…2.5 mm
2
) (all terminals)
4. Tightening torques: 0.4 lb-ft (0.5…0.6 N•m)
PID control, single motor
Input signals
Output signals
•
Setpoint selected from: control panel setpoint/constant
setpoint /analog input (AI1)
•
Analog output AO1: Output frequency
•
PID feedback (AI2)
•
Analog output AO2: Motor current
•
Start/stop selection (DI1)
•
Relay output 1: Damper control
•
Constant speed/frequency selection (DI3)
•
Relay output 2: Running
•
Start interlock 1 (DI4)
•
Relay output 3: Fault (-1)
1)
Connected with jumpers at the factory.
2)
Only frames R6…R9 have terminals 40 and 41 for external 24 V AC/DC input.
X1
Reference voltage and analog inputs and outputs
1
SCR
Signal cable shield (screen)
2
AI1
Analog input 1
3
AGND
Analog input circuit common
4
+10V
Reference voltage 10 V DC
5
AI2
Actual feedback:
0 to 20 mA
6
AGND
Analog input circuit common
7
AO1
Output frequency:
0 to 10 V
8
AO2
Motor current:
0 to 20 mA
9
AGND
Analog output circuit common
X2 & X3
Aux. voltage output and programmable digital inputs
10
+24V
Aux. voltage 24 V DC, max. 250 mA
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
13
DI1
Stop (0)/Start (1)
14
DI2
Not configured
15
DI3
Constant frequency/speed selection
16
DI4
Start interlock 1 (1 = allow start)
17
DI5
Not configured
18
DI6
Not configured
X6, X7, X8
Relay
outputs
19
RO1C
Damper control
250 V AC / 30 V DC
2 A
20
RO1A
21
RO1B
22
RO2C
Running
250 V AC / 30 V DC
2 A
23
RO2A
24
RO2B
25
RO3C
Fault (-1)
250 V AC / 30 V DC
2 A
26
RO3A
27
RO3B
X5
Embedded fieldbus
29
B+
Embedded fieldbus, EFB (EIA-485)
30
A-
31
DGND
S4
TERM
Termination switch
S5
BIAS
Bias resistors switch
X4
Safe torque off
34
OUT1
Safe torque off
35
OUT2
36
SGND
37
IN1
38
IN2
+10 V
+24 V
+
-
4…20 mA temp.
feedback signal
Start/Stop signal
Safety
Run status
Fault status
Energize damper
19 connected to 21
Running
22 connected to 24
Fault condition
25 connected to 26