![background image](http://html1.mh-extra.com/html/abb/ach580-series/ach580-series_installation-operation-and-maintenance-manual_3357302105.webp)
ACH580 Installation, Operation and Maintenance Manual
105
ACH580 E-Clipse Bypass
460 Volt fuses for vertical enclosures
575 Volt fuses for vertical enclosures
Type Code
1
Nominal Output
Ratings
Base
Drive
Frame
Size
Internal Drive
Fuse Rating
External Fuse for
Disconnect Option
Drive
Current
Package
Power
Class
Max
Current
Rating
Class
Max
Current
Rating
A
HP
460 Volts
ACH580-VxR-02A1-4
2.1
1
R1
Class CC
15A
Class J
15A
ACH580-VxR-03A0-4
3.0
1.5
R1
Class CC
15A
Class J
15A
ACH580-VxR-03A5-4
3.5
2
R1
Class CC
15A
Class J
15A
ACH580-VxR-04A8-4
4.8
3
R1
Class CC
15A
Class J
15A
ACH580-VxR-07A6-4
7.6
5
R1
Class CC
15A
Class J
20A
ACH580-VxR-012A-4
12
7.5
R1
Class CC
15A
Class J
25A
ACH580-VxR-014A-4
14
10
R2
Class CC
30A
Class J
35A
ACH580-VxR-023A-4
23
15
R2
Class CC
30A
Class J
45A
ACH580-VxR-027A-4
27
20
R3
Class T
40A
Class J
60A
ACH580-VxR-034A-4
34
25
R3
Class T
60A
Class J
60A
ACH580-VxR-044A-4
44
30
R3
Class T
60A
Class J
60A
ACH580-VxR-052A-4
52
40
R4
Class T
80A
Class J
100A
ACH580-VxR-065A-4
65
50
R4
Class T
90A
Class J
100A
ACH580-VxR-077A-4
77
60
R4
Class T
100A
Class J
100A
1) “VxR” represents both VCR and VDR.
Type Code
1
Nominal Output
Ratings
Base
Drive
Frame
Size
Internal Drive
Fuse Rating
External Fuse for
Disconnect Option
Drive
Current
Package
Power
Class
Max Current
Rating
Class
Max Current
Rating
A
HP
575 Volts
2
ACH580-VxR-02A7-6
2.7
2
R2
Class CC
30A
Class J
15A
ACH580-VxR-03A9-6
3.9
3
R2
Class CC
30A
Class J
15A
ACH580-VxR-06A1-6
6.1
5
R2
Class CC
30A
Class J
15A
ACH580-VxR-09A0-6
9
7.5
R2
Class CC
30A
Class J
20A
ACH580-VxR-011A-6
11
10
R2
Class CC
30A
Class J
25A
ACH580-VxR-017A-6
17
15
R2
Class CC
30A
Class J
40A
ACH580-VxR-022A-6
22
20
R3
Class T
40A
Class J
50A
ACH580-VxR-027A-6
27
25
R3
Class T
40A
Class J
60A
1) “VxR” represents both VCR and VDR.
2) VCR is rated 600Y/347V. For use on a solidly grounded Wye source only.