Separate control cable ducts
Put 24 V DC and 230 V AC (120 V AC) control cables in separate ducts, unless the
24 V DC cable is insulated for 230 V AC (120 V AC) or insulated with an insulation
sleeving for 230 V AC (120 V AC).
24 V DC
230 V AC
(120 V AC)
230 V AC
(120 V AC)
24 V DC
Implementing short-circuit and thermal overload protection
■
Protecting the drive and input power cable in short-circuits
Use the fuses specified for the drive in the technical data. Make sure that also the electric
power supply network meets the specification (minimum allowed short-circuit current
that the fuse selection is based on).
The fuses restrict drive damage and prevent damage to adjoining equipment in case of
a short-circuit inside the drive. When located at the distribution board, the fuses also
protect the input power cable against short circuits.
See the drive technical data for alternative short-circuit protections.
■
Protecting the motor and motor cable in short-circuits
The drive protects the motor cable and motor in a short-circuit situation when the motor
cable is sized according to the nominal current of the drive. No additional protection
devices are needed.
■
Protecting the drive, and the input power and motor cables against
thermal overload
If the cables have the correct size for the nominal current, the drive protects itself and
the input and motor cables against thermal overload. No additional thermal protection
devices are needed.
WARNING!
If the drive is connected to multiple motors, use a separate motor thermal overload
device for protecting each motor cable and motor against overload. The drive
overload protection is for the sum of the total motor load. It may not trip due to an
overload in one motor.
Guidelines for planning the electrical installation 55
Summary of Contents for ACH480
Page 1: ... ABB DRIVES FOR HVAC ACH480 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 14: ...14 ...
Page 22: ...22 ...
Page 28: ...28 ...
Page 38: ...38 ...
Page 44: ...44 ...
Page 60: ...60 ...
Page 86: ...86 ...
Page 110: ...110 ...
Page 114: ...114 ...
Page 122: ...122 ...
Page 156: ...Frame R1 Frame R1 front side IP20 UL open type 156 Dimension drawings ...
Page 157: ... Frame R1 bottom rear IP20 UL open type Dimension drawings 157 ...
Page 158: ... Frame R1 front side UL Type 1 kit installed 158 Dimension drawings ...
Page 159: ... Frame R1 bottom rear UL Type 1 kit installed Dimension drawings 159 ...
Page 160: ...Frame R2 Frame R2 front side IP20 UL open type 160 Dimension drawings ...
Page 161: ... Frame R2 bottom rear IP20 UL open type Dimension drawings 161 ...
Page 162: ... Frame R2 front side UL Type 1 kit installed 162 Dimension drawings ...
Page 163: ... Frame R2 bottom rear UL Type 1 kit installed Dimension drawings 163 ...
Page 164: ...Frame R3 Frame R3 front side IP20 UL open type 164 Dimension drawings ...
Page 165: ... Frame R3 bottom rear IP20 UL open type Dimension drawings 165 ...
Page 166: ... Frame R3 front side UL Type 1 kit installed 166 Dimension drawings ...
Page 167: ... Frame R3 bottom rear UL Type 1 kit installed Dimension drawings 167 ...
Page 168: ...Frame R4 Frame R4 front side IP20 UL open type 168 Dimension drawings ...
Page 169: ... Frame R4 bottom rear IP20 UL open type Dimension drawings 169 ...
Page 170: ... Frame R4 front side UL Type 1 kit installed 170 Dimension drawings ...
Page 171: ... Frame R4 bottom rear UL Type 1 kit installed Dimension drawings 171 ...
Page 172: ...172 ...
Page 180: ...180 ...
Page 198: ... Declaration of conformity 198 The Safe torque off function ...
Page 206: ...Dimensions 206 BIO 01 I O extension module ...
Page 212: ...Dimensions 3AXD50000031148 rev A 212 BREL 01 relay output extension module ...