Derating factor
UL (NEC)
type
ACH480-
04-…
12 kHz
8 kHz
< 4 kHz
0.49
0.65
1.0
034A-4
0.49
0.66
1.0
042A-4
Fuses
The tables list the fuses for protection against short-circuits in the input power cable or
drive. The operating time depends on the supply network impedance, and the
cross-sectional area and length of the supply cable.
Do not use fuses that have a higher current rating than specified in the table. You can
use fuses from other manufacturers, if they meet the ratings, and if the melting curve
of the fuse does not exceed the melting curve of the fuse mentioned in the table.
■
IEC fuses
Either fuse type can be used if it operates rapidly enough.
gG fuses (IEC)
Make sure that the operating time of the fuse is less than 0.5 seconds. Obey the local
regulations.
gG fuses
Min.
short-circuit
current
1)
Drive input
current
IEC type
ACH480-04-
IEC
60269
size
ABB type
Voltage
rating
I2t
Nominal
current
V
A2s
A
A
A
3-phase
U
N = 400 V
000
OFAF000H6
500
110
6
48
4.2
02A7-4
000
OFAF000H6
500
110
6
48
5.3
03A4-4
000
OFAF000H10
500
360
10
80
6.4
04A1-4
000
OFAF000H10
500
360
10
80
9.0
05A7-4
000
OFAF000H16
500
740
16
128
11.5
07A3-4
000
OFAF000H16
500
740
16
128
15.0
09A5-4
000
OFAF000H25
500
2500
25
200
20.2
12A7-4
000
OFAF000H32
500
4500
32
256
27.2
018A-4
000
OFAF000H50
500
15500
50
400
40.0
026A-4
000
OFAF000H63
500
20000
63
504
45.0
033A-4
000
OFAF000H80
500
36000
80
640
50.0
039A-4
000
OFAF000H100
500
65000
100
800
56.0
046A-4
000
OFAF000H100
500
65000
100
800
60.0
050A-4
1) Minimum permitted short-circuit current of the electrical power network
130 Technical data
Summary of Contents for ACH480
Page 1: ... ABB DRIVES FOR HVAC ACH480 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 14: ...14 ...
Page 22: ...22 ...
Page 28: ...28 ...
Page 38: ...38 ...
Page 44: ...44 ...
Page 60: ...60 ...
Page 86: ...86 ...
Page 110: ...110 ...
Page 114: ...114 ...
Page 122: ...122 ...
Page 156: ...Frame R1 Frame R1 front side IP20 UL open type 156 Dimension drawings ...
Page 157: ... Frame R1 bottom rear IP20 UL open type Dimension drawings 157 ...
Page 158: ... Frame R1 front side UL Type 1 kit installed 158 Dimension drawings ...
Page 159: ... Frame R1 bottom rear UL Type 1 kit installed Dimension drawings 159 ...
Page 160: ...Frame R2 Frame R2 front side IP20 UL open type 160 Dimension drawings ...
Page 161: ... Frame R2 bottom rear IP20 UL open type Dimension drawings 161 ...
Page 162: ... Frame R2 front side UL Type 1 kit installed 162 Dimension drawings ...
Page 163: ... Frame R2 bottom rear UL Type 1 kit installed Dimension drawings 163 ...
Page 164: ...Frame R3 Frame R3 front side IP20 UL open type 164 Dimension drawings ...
Page 165: ... Frame R3 bottom rear IP20 UL open type Dimension drawings 165 ...
Page 166: ... Frame R3 front side UL Type 1 kit installed 166 Dimension drawings ...
Page 167: ... Frame R3 bottom rear UL Type 1 kit installed Dimension drawings 167 ...
Page 168: ...Frame R4 Frame R4 front side IP20 UL open type 168 Dimension drawings ...
Page 169: ... Frame R4 bottom rear IP20 UL open type Dimension drawings 169 ...
Page 170: ... Frame R4 front side UL Type 1 kit installed 170 Dimension drawings ...
Page 171: ... Frame R4 bottom rear UL Type 1 kit installed Dimension drawings 171 ...
Page 172: ...172 ...
Page 180: ...180 ...
Page 198: ... Declaration of conformity 198 The Safe torque off function ...
Page 206: ...Dimensions 206 BIO 01 I O extension module ...
Page 212: ...Dimensions 3AXD50000031148 rev A 212 BREL 01 relay output extension module ...