Free space requirements
Free space requirement
Frame
Sides
2)
Below
Above
1)
in
mm
in
mm
in
mm
0
0
3
75
3
75
All
1) Drives with the optional UL Type 1 kit: 50 mm (2 in), measured from the top of the hood.
2) A side-mounted option module requires 20 mm (0.8 in) of free space on the right side of the drive.
Losses, cooling data and noise
Drives with frame size R1…R4 have a cooling fan. The air flow direction is from bottom
to top.
The tables show the heat dissipation in the main circuit at nominal load, and in the
control circuit with minimum load (I/O and panel not in use) and maximum load (all digital
inputs in the on state and the panel, fieldbus and fan in use). The total heat dissipation
is the sum of the heat dissipation in the main and control circuits.
Noise
Air flow
Heat dissipation
IEC type
ACH480-04-
Main and
control
circuit
max.
Control
circuit
max.
2)
Control
circuit
min.
1)
Main circuit
at rated
current
dB(A)
m3/h
W
W
W
W
3-phase
U
N = 400 V
63
57
55
20
9
35
02A7-4
63
57
62
20
9
42
03A4-4
63
57
70
20
9
50
04A1-4
63
57
88
20
9
68
05A7-4
63
57
108
20
9
88
07A3-4
63
57
135
20
9
115
09A5-4
59
63
178
20
9
158
12A7-4
66
128
230
22
11
208
018A-4
66
128
344
22
11
322
026A-4
69
150
465
30
18
435
033A-4
69
150
566
30
18
537
039A-4
69
150
668
30
18
638
046A-4
69
150
668
30
18
638
050A-4
1) Without I/O module or fieldbus adapter installed
2) With I/O module and fieldbus adapter installed
138 Technical data
Summary of Contents for ACH480
Page 1: ... ABB DRIVES FOR HVAC ACH480 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 14: ...14 ...
Page 22: ...22 ...
Page 28: ...28 ...
Page 38: ...38 ...
Page 44: ...44 ...
Page 60: ...60 ...
Page 86: ...86 ...
Page 110: ...110 ...
Page 114: ...114 ...
Page 122: ...122 ...
Page 156: ...Frame R1 Frame R1 front side IP20 UL open type 156 Dimension drawings ...
Page 157: ... Frame R1 bottom rear IP20 UL open type Dimension drawings 157 ...
Page 158: ... Frame R1 front side UL Type 1 kit installed 158 Dimension drawings ...
Page 159: ... Frame R1 bottom rear UL Type 1 kit installed Dimension drawings 159 ...
Page 160: ...Frame R2 Frame R2 front side IP20 UL open type 160 Dimension drawings ...
Page 161: ... Frame R2 bottom rear IP20 UL open type Dimension drawings 161 ...
Page 162: ... Frame R2 front side UL Type 1 kit installed 162 Dimension drawings ...
Page 163: ... Frame R2 bottom rear UL Type 1 kit installed Dimension drawings 163 ...
Page 164: ...Frame R3 Frame R3 front side IP20 UL open type 164 Dimension drawings ...
Page 165: ... Frame R3 bottom rear IP20 UL open type Dimension drawings 165 ...
Page 166: ... Frame R3 front side UL Type 1 kit installed 166 Dimension drawings ...
Page 167: ... Frame R3 bottom rear UL Type 1 kit installed Dimension drawings 167 ...
Page 168: ...Frame R4 Frame R4 front side IP20 UL open type 168 Dimension drawings ...
Page 169: ... Frame R4 bottom rear IP20 UL open type Dimension drawings 169 ...
Page 170: ... Frame R4 front side UL Type 1 kit installed 170 Dimension drawings ...
Page 171: ... Frame R4 bottom rear UL Type 1 kit installed Dimension drawings 171 ...
Page 172: ...172 ...
Page 180: ...180 ...
Page 198: ... Declaration of conformity 198 The Safe torque off function ...
Page 206: ...Dimensions 206 BIO 01 I O extension module ...
Page 212: ...Dimensions 3AXD50000031148 rev A 212 BREL 01 relay output extension module ...