Make sure that …
The supply voltage matches the nominal input voltage of the drive. See the type designation
label.
The insulation resistance of the input power cable, motor cable and motor is measured
according to local regulations.
The drive is attached securely on an even, vertical and non-flammable wall.
The cooling air flows freely in and out of the drive.
If the drive is connected to a network other than a symmetrically grounded TN-S system:
You have done all the required modifications (for example, you may need to disconnect
the EMC filter or ground-to-phase varistor). See the electrical installation instructions.
Appropriate AC fuses and main disconnector are installed.
There is an adequately sized protective earth (ground) conductor(s) between the drive
and the switchboard, the conductor is connected to correct terminal, and the terminal is
tightened to the correct torque.
Proper grounding has also been measured according to the regulations.
The input power cable is connected to the correct terminals, the phase order is correct,
and the terminals are tightened to the correct torque.
There is an adequately sized protective earth (ground) conductor between the motor and
the drive, and the conductor is connected to the correct terminal, and the terminal is
tightened to the correct torque.
Proper grounding has also been measured according to the regulations.
The motor cable is connected to the correct terminals, the phase order is correct, and the
terminals are tightened to the correct torque.
The motor cable is routed away from other cables.
No power factor compensation capacitors are connected to the motor cable.
If an external brake resistor is connected to the drive: There is an adequately sized pro-
tective earth (ground) conductor between the brake resistor and the drive, and the con-
ductor is connected to the correct terminal, and the terminals are tightened to the correct
torque.
Proper grounding has also been measured according to the regulations.
If an external brake resistor is connected to the drive: The brake resistor is connected to
the correct terminals, and the terminals are tightened to the correct torque.
If an external brake resistor is connected to the drive: The brake resistor cable is routed
away from other cables.
The control cables are connected to the correct terminals, and the terminals are tightened
to the correct torque.
112 Installation checklist of the drive
Summary of Contents for ACH480
Page 1: ... ABB DRIVES FOR HVAC ACH480 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 14: ...14 ...
Page 22: ...22 ...
Page 28: ...28 ...
Page 38: ...38 ...
Page 44: ...44 ...
Page 60: ...60 ...
Page 86: ...86 ...
Page 110: ...110 ...
Page 114: ...114 ...
Page 122: ...122 ...
Page 156: ...Frame R1 Frame R1 front side IP20 UL open type 156 Dimension drawings ...
Page 157: ... Frame R1 bottom rear IP20 UL open type Dimension drawings 157 ...
Page 158: ... Frame R1 front side UL Type 1 kit installed 158 Dimension drawings ...
Page 159: ... Frame R1 bottom rear UL Type 1 kit installed Dimension drawings 159 ...
Page 160: ...Frame R2 Frame R2 front side IP20 UL open type 160 Dimension drawings ...
Page 161: ... Frame R2 bottom rear IP20 UL open type Dimension drawings 161 ...
Page 162: ... Frame R2 front side UL Type 1 kit installed 162 Dimension drawings ...
Page 163: ... Frame R2 bottom rear UL Type 1 kit installed Dimension drawings 163 ...
Page 164: ...Frame R3 Frame R3 front side IP20 UL open type 164 Dimension drawings ...
Page 165: ... Frame R3 bottom rear IP20 UL open type Dimension drawings 165 ...
Page 166: ... Frame R3 front side UL Type 1 kit installed 166 Dimension drawings ...
Page 167: ... Frame R3 bottom rear UL Type 1 kit installed Dimension drawings 167 ...
Page 168: ...Frame R4 Frame R4 front side IP20 UL open type 168 Dimension drawings ...
Page 169: ... Frame R4 bottom rear IP20 UL open type Dimension drawings 169 ...
Page 170: ... Frame R4 front side UL Type 1 kit installed 170 Dimension drawings ...
Page 171: ... Frame R4 bottom rear UL Type 1 kit installed Dimension drawings 171 ...
Page 172: ...172 ...
Page 180: ...180 ...
Page 198: ... Declaration of conformity 198 The Safe torque off function ...
Page 206: ...Dimensions 206 BIO 01 I O extension module ...
Page 212: ...Dimensions 3AXD50000031148 rev A 212 BREL 01 relay output extension module ...