364xS User’s Manual
41
Operation
Note
The Main Menu, the Sub Menu, the Sub Sub Menu and the Utility view are also indicated on the display with
a number. The menu navigation can be described also as a sequence of the corresponding numbers that is
called “Digital LCD Integral Display Keys sequence“
In any case the following table better details the available functions. The instructions of this manual further
define the Digital LCD Integral Display menu sequence to run an operation.
Display indication
Description
Level
Type
Easy Setup
This function helps the end user to run the
instrument basic configuration
Main Menu
Language
Set the display language
Utility
Enumerated
Pressure Polarity
Set the pressure transmitter High pressure side
Utility
Enumerated
Engineering Unit
Set the Engineering Variable unit
Utility
Enumerated
Set LRV
Set the Lower Range Value
Utility
Numerical
Set URV
Set the Upper Range value
Utility
Numerical
Transfer Function Type
Set the transmitter output transfer function
Utility
Enumerated
Lin Point
Set the point up to the output is linear with input if
the Square root is set
Utility
Numerical
Low Flow Cut Off
Set the point up to the output is zero for any input
value, when square root is selected
Utility
Numerical
Auto-Set Zero Scaling
Set the Primary Variable at Zero
Utility
Auto Adjust
Damping
Set the damping value
Utility
Manual Adjust
Device Config
This function provides all the settings related to the
device configuration
Main Menu
Rerange
This function provides the transmitter rerange
Sub Menu
Rerange with pressure
This function provides the transmitter rerange
when a pressure source is available
Sub Sub
Menu
Set LRV (0%)
Set the Low Range Value at the applied pressure
Utility
Auto Adjust
Set URV (100%)
Set the Upper Range Value at the applied pressure
Utility
Auto Adjust
Rerange no pressure
This function provides the transmitter rerange
when no pressure source is available
Sub Sub
Menu
Engineering Unit
Select the engineering units for the Engineering
variable
Utility
Enumerated
Set LRV
Set the Lower Range Value at the defined value
Utility
Numerical
Set URV
Set the Upper Range Value at the defined value
Utility
Numerical
Percentage Rerange
This function provides the transmitter rerange
when any pressure source is available related to
the percentage value
Sub Sub
Menu
Set LRV (0%)
Set the Lower Range Value at the defined value in
percentage
Utility
Numerical
Set URV (100%)
Set the Upper Range Value at the defined value in
percentage
Utility
Numerical
PV Scaling
This function provides the Primary Variable Scaling
Sub Menu
Auto-Set Zero Scaling
Shift the primary variable to zero
Utility
Auto Adjust