![ABB 2600T Pressure Transmitter Series User Manual Download Page 28](http://html.mh-extra.com/html/abb/2600t-pressure-transmitter-series/2600t-pressure-transmitter-series_user-manual_3724028.webp)
364xS User’s Manual
28
Configuration
To set the Transmitter LRV with reference pressure:
Set the transmitter applied pressure as for Lower Range value (0%). Navigate the Digital LCD Integral
Display menu, select
Device Config
>
Rerange
>
Rerange with pressure
>
Set LRV (0%)
.
Select
OK
to start the autoadjust.
)
Digital LCD Integral Display Keys sequence to set the LRV wih pressure: 2 – 1 – 1 – 1 – OK
Set the LRV by CoMeter
LRV configuration by CoMeter is available with the 695 Field Indicator. Please refer to the device manual for
the appropriate operations.
Set the LRV by HHT
LRV configuration by Hand Held Terminal is available. Please refer to the device manual for the appropriate
operations.
Set the LRV by PC
LRV configuration by PC is available using dedicated Software. ABB can provide the references and the
Software. Please refer to the Software instructions for the appropriate operations.
Set the URV
When a URV different from the selected is needed it is possible to change it following one of the methods
described in the next paragraphs.
Set the URV by Local Keys
Set the transmitter applied pressure as for Upper
Range Value. When the applied pressure is
stable push the Span local adjustment key (S)
located on the terminal block and release. After
this operation the reading shall move to 20 mA. If
no changes occur repeat the operation.
Set the URV by Digital LCD Integral Display
To set the URV reading of the Digital LCD Integral Display (the engineering units have to be selected):
Navigate the Digital LCD Integral Display menu, select
Display
>
Display settings
>
Display URV (100%)
,
and the Span values may be available.
Select the desired value and confirm.
)
Digital LCD Integral Display Keys sequence to set the Display URV : 3 – 7 – 3 - Edit
To set the Transmitter URV without reference pressure:
Navigate the Digital LCD Integral Display menu, select
Device Config
>
Rerange
>
Rerange no pressure
>
Set URV
, and the URV values may be available
Select the desired value and confirm.
)
Digital LCD Integral Display Keys sequence to set the URV wihout pressure: 2 – 1 – 2 – 3 – Edit
Summary of Contents for 2600T Pressure Transmitter Series
Page 1: ...InstrumentationIT 2600T Pressure Transmitter family ABB User s Manual 364DS and 364PS Models ...
Page 7: ...364xS User s Manual 7 This page has been intentionally left blank ...
Page 72: ...364xS User s Manual 72 Additional Safety ...