Installation
Level measurement with closed tanks and non
condensable fluids (dry leg)
1. Mount the transmitter at the same height or below
the lowest level to be measured.
2. Connect the
High Pressure Side (P2 as default)
of the transmitter to the bottom of the tank
3.
Connect the
Low Pressure Side (P1 as default)
of
the transmitter to the upper part of the tank, above
the maximum level of the tank.
Level measurement with closed tanks and
condensable fluids (wet leg)
1. Mount the transmitter at the same height or below
the lowest level to be measured.
2. Connect the
High Pressure Side (P2 as default)
of the transmitter to the bottom of the tank
3. Connect the
Low Pressure Side (P1 as default)
of
the transmitter to the upper part of the tank.
4. Fill the vertical section of the connecting line to the
upper part of the tank with a compatible liquid
through the dedicated filling tee.
Filling
tee
Gate
valve
Drain
Valve
Wet leg
Gate
valve
Gate
valve
Gate
valve
Condensate trap
(optional)
minimum level
maximum level
minimum level
maximum level