364xS User’s Manual
22
Configuration
Configuration
Default configuration
The data default configuration at the product delivery is the following:
Pressure Polarity:
P2 High pressure
Damping: 1
second
Units: kPa
LRV: 0
kPa
URV:
equal to URL
Totalizer: OFF
Transfer function:
linear
Hardware setting:
Write protect mode in OFF, Failsafe direction High
Low saturation current: 3.8 mA
High saturation current: 20.5 mA
Low fail current:
3.7 mA
High fail current:
22 mA
Easy Setup
To facilitate commissioning the 364 Display has the capability to run a sequence of predefined setup steps
with the main configuration settings.
When you start the Easy Setup you must continue up to the end to exit.
To start the Easy Setup:
Navigate the Digital LCD Integral Display menu, select
Easy Setup
.
)
Digital LCD Integral Display Keys sequence to start the Easy Setup: 1
Define the language
If the desired language is different from the indicated language select
Edit
then scroll the desired language
(see the following table) with the up and down keys and confirm with
OK
. Select
Next
to continue.
English
Spanish
Italian
German
French
Define the Pressure Polarity
If the desired High Pressure side is different from the indicated select
Edit
then scroll the desired High
Pressure side (see the following table) with the up and down keys and confirm with
OK
. Select
Next
to
continue.
P2 = High pressure
the high pressure side is the pressure chamber indicated as P2 on
the transmitter body. The output pressure will be P2 – P1
P1 = High pressure
the high pressure side is the pressure chamber indicated as P1 on
the transmitter body. The output pressure will be P1 – P2
Define the Engineering Unit
If the desired Engineering Unit is different from the indicated, select
Edit
then scroll the desired unit (see the
following table) with the up and down keys and confirm with
OK
. Select
Next
to continue.
mbar
millibar
mmH2O°C
millimeter of water at 4 degrees Celsius
g/cm
2
grams per square centimeter
inH2O°F
inches of water at 68 degrees Fahrenheit (20°C)
Kg/cm
2
kilo grams per square centimeter
inHg°C
inches of mercury at 0 degrees Celsius
Pa
pascal
ftH2O°F
feet of water at 68 degrees Fahrenheit (20°C)
kPa
kilopascal
mmH2O°F
millimeter of water at 68 degrees Fahrenheit (20°C)
torr
torr
mmHg°C
millimeter of mercury at 0 degrees Celsius
atm
atmosphere
psi
pounds per square inch
MPa
Megapascal
bar
bars
inH2O°C
inches of water at 4 degrees Celsius