364xS User’s Manual
29
Configuration
To set the Transmitter URV with reference pressure:
Set the transmitter applied pressure as for Upper Range value (100%). Navigate the Digital LCD Integral
Display menu, select
Device Config
>
Rerange
>
Rerange with pressure
>
Set URV (100%)
.
Select
OK
to start the autoadjust.
)
Digital LCD Integral Display Keys sequence to set the URV wih pressure: 2 – 1 – 1 – 2 – OK
Set the URV by CoMeter
URV configuration by CoMeter is available with the 695 Field Indicator. Please refer to the device manual for
the appropriate operations.
Set the URV by HHT
URV configuration by Hand Held Terminal is available. Please refer to the device manual for the appropriate
operations.
Set the URV by PC
URV configuration by PC is available using dedicated Software. ABB can provide the references and the
Software. Please refer to the Software instructions for the appropriated operations.
Set the Totalizer
When a Totalizer setting different from the selected is needed it is possible to change it following one of the
methods described in the next paragraphs.
In case the Totalizer is used in Bidirectional Flow the Totalizer LRV (0%) and the Totalizer URV (100%) have
to be equal in absolute value.
Set the Totalizer by Digital LCD Integral Display
To set the Totalizer LRV (0%):
Navigate the Digital LCD Integral Display menu, select
Totalizer
>
Totalizer setting
>
Totalizer LRV (0%)
,
and the value will be available. To modify select
Edit
then scroll the desired value for the digit in reverse
color with the up and down keys and confirm with
Next.
Repeat the operation for the seven digits and
confirm with
OK.
Note: the minimum and the maximum values to introduce is indicated on the display.
)
Digital LCD Integral Display Keys sequence to set the Totalizer LRV : 4 – 3 – 1 – Edit
To set the Totalizer URV (100%):
Navigate the Digital LCD Integral Display menu, select
Totalizer
>
Totalizer setting
>
Totalizer URV (100%)
,
and the value will be available. To modify select
Edit
then scroll the desired value for the digit in reverse
color with the up and down keys and confirm with
Next.
Repeat the operation for the seven digits and
confirm with
OK.
Note: the minimum and the maximum values to introduce are indicated on the display.
)
Digital LCD Integral Display Keys sequence to set the Totalizer URV : 4 – 3 – 2 – Edit
To set the Input Totalizer Engineering Units:
Navigate the Digital LCD Integral Display menu, select
Totalizer
>
Totalizer setting
>
Input Eng. Units
, and
the used Totalizer Engineering Units will be available. To modify select
Edit
then scroll the desired unit (see
the following table) with the up and down keys and confirm with
OK
.
)
Digital LCD Integral Display Keys sequence to set the Totalizer Input Engineering Units : 4 – 3 – 3 – Edit