Zone
Zone
VCC-X CONFIGURATION
VCC-X Operator Interface SD
38
VCC-X Con
fi
guration Screens
Con
fi
guration Screens #78-84 - VCC-X Relay
Con
fi
guration Screens
VCC-X Cnfg ID #
On-Board Relay (2-8)
Not Used
USE < or > TO CHANGE
Relay #1 is not con
fi
gurable as it is reserved for the Supply Air Fan.
Relays #2-#8 are con
fi
gurable for the following options (See
Table
5, page 39
for Relay descriptions):
•
Not Used (Default)
•
Cool Stage
•
Heat
Stage
•
HP Aux Heat
•
HP Emer Heat
•
Mod Heat Enable
•
Mod Cool Enable
•
Warmup / Cooldown
•
ReHeat
•
PreHeat
•
Low
Ambient
•
Exhaust Fan
•
Economizer
•
Heat Wheel
•
Occupied
Mode
•
Override Mode
•
Alarm
Active
Relays #2 through #8 can be individually con
fi
gured. Only forms
of Heating and Cooling can be con
fi
gured with multiple relays for
staging. If any other option is selected more than once, it will sim-
ply activate redundant relays, but no multiple staging will occur.
Default is Not Used.
Con
fi
guration Screens #85-89 - EM1 Relay
Con
fi
guration Screens
VCC-X Cnfg ID #
EM1 Relay (1-5)
Not Used
USE < or > TO CHANGE
EM1 Relays #1-#5 are con
fi
gurable for the following options (See
Table 5, page 39
for Relay descriptions):
•
Not Used (Default)
•
Cool Stage
•
Heat
Stage
•
HP Aux Heat
•
HP Emer Heat
•
Mod Heat Enable
•
Mod Cool Enable
•
Warmup / Cooldown
•
ReHeat
•
PreHeat
•
Low
Ambient
•
Exhaust Fan
•
Economizer
•
Heat Wheel
•
Occupied
Mode
•
Override Mode
•
Alarm
Active
Relays #1 through #5 can be individually con
fi
gured. Only forms of
Heating and Cooling can be con
fi
gured with multiple relays for
staging. If any other option is selected more than once, it will simply
activate redundant relays, but no multiple staging will occur.
Default
is Not Used.
Con
fi
guration Screens #90-101 - E-BUS
12 Relay Con
fi
guration Screens
VCC-X Cnfg ID #
12 Rly Bd Relay (1-12)
Not Used
USE < or > TO CHANGE
The E-BUS 12 Relay Expansion Board Relays #1-#12 are con
fi
gu-
rable for the following options (See
Table 5, page 39
for Relay
descriptions):
•
Not Used (Default)
•
Cool Stage
•
Heat
Stage
•
HP Aux Heat
•
HP Emer Heat
•
Mod Heat Enable
•
Mod Cool Enable
•
Warmup / Cooldown
•
ReHeat
•
PreHeat
•
Low
Ambient
•
Exhaust Fan
•
Economizer
•
Heat Wheel
•
Occupied
Mode
•
Override Mode
•
Alarm
Active
Relays #1 through #12 can be individually con
fi
gured. Only forms
of Heating and Cooling can be con
fi
gured with multiple relays for
staging. If any other option is selected more than once, it will sim-
ply activate redundant relays, but no multiple staging will occur.
Default is Not Used.