VCC-X Operator Interface SD
VCC-X CONFIGURATION
33
All Modes Occupied
—This is Occupied Mode
Dehumidi
fi
cation Priority. The unit can enter
Dehumidi
fi
cation during Cooling, Heating, or Vent
Modes, but only while in Occupied operation.
All Modes Anytime
—This is Occupied and
Unoccupied
Dehumidi
fi
cation Priority. The unit can
enter
Dehumidi
fi
cation during Cooling, Heating, or Vent
Modes while in Occupied or Unoccupied operation.
For units controlled by space humidity sensors, Dehumidi
fi
cation
is initiated based on an Indoor Humidity Setpoint. For 100% OA
units (MUA), Occupied Dehumidi
fi
cation is initiated based on
an Outdoor Air Dewpoint Setpoint. For MUA units, Unoccupied
Dehumidi
fi
cation can only occur if the unit is con
fi
gured for Night
Setback recirculating operation and has a Space Humidity sensor
and a Space Humidity Setpoint.
Con
fi
guration Screen #45 - Humidity Control
Sensor Type
VCC-X Cnfg ID #
Humidity Control
Sensor: Space
USE < or > TO CHANGE
Select
Space, Return, or Outdoor if an E-BUS Humidity Sensor is
installed.
Default is Space.
Con
fi
guration Screen #46 - Reheat Type
VCC-X Cnfg ID #
Reheat Control
None
USE < or > TO CHANGE
This con
fi
guration option is available if Dehumidi
fi
cation has been
con
fi
gured. If you need Reheat in the Dehumidi
fi
cation mode, this
screen allows you to con
fi
gure what kind of reheat will be used.
The output(s) will be staged or modulated to maintain the Active
Supply Air Setpoint.
Default is None.
Select
the type of reheat that
will be used during dehumidi
fi
cation.
None
—No reheat.
On/Off HGR Relay
—Single On/Off Reheat stage
(Reheat Relay).
Mod HGR
—Modulating Hot Gas Reheat (MHGR)
Unit Heat
—Using the unit’s heat as Reheat when Hot
Gas Reheat is not available.
Mod HGR + Unit Heat
—Using MHGR as the 1
st
form of Reheat, supplemented by unit Heat if necessary.
On/Off HGR + Unit Heat
—Using “Reheat Relay”
stage as the 1
st
form of Reheat, supplemented by unit
Heat if necessary.
VCC-X Con
fi
guration Screens
Con
fi
guration Screen #47 - Type of Air
fl
ow
Station
VCC-X Cnfg ID #
Airflow
Station: Paragon
USE < or > TO CHANGE
S
elect the type of Air
fl
ow Monitoring Station you are using, if any.
Selections are Ebtron or Paragon.
Default is Paragon
.
Con
fi
guration Screen #48 - Monitor Outdoor
Air Air
fl
ow
VCC-X Cnfg ID #
Monitor OA Airflow
NO
USE < or > TO CHANGE
Select
YES if you have an Air
fl
ow Monitoring station measuring the
CFM of the Outdoor Air air
fl
ow stream of this unit.
Default is NO.
Con
fi
guration Screen #49 - Control Outdoor
Air CFM
VCC-X Cnfg ID #
Control Outdoor Air
CFM: NO
USE < or > TO CHANGE
Select
YES if you have an Air
fl
ow Monitoring station and are
controlling the Outdoor Air Damper to an air
fl
ow (CFM) Setpoint.
Default is NO.
Con
fi
guration Screen #50 - Outdoor Air
fl
ow
Duct Size
VCC-X Cnfg ID #
Outdoor Airflow Duct
Size: 0.00
[ In Square Feet ]
For the controller to properly calculate the Outdoor Air CFM, you
need to
enter
the area in square feet of the Outdoor Air duct/damper.
When measuring the Outdoor Air duct damper area, be sure to mea-
sure the inside dimensions of the damper. The duct size needs to be
accurate to two decimal places. The more accurate the measurements,
the more accurate the CFM reading will be.
Default is 0.
Description
Minimum
Default
Maximum
Outdoor Air Air
fl
ow Duct Size
0
0
200.00