VCC-X Operator Interface SD
VCC-X CONFIGURATION
37
VCC-X Con
fi
guration Screens
See the
VCC-X Controller Technical Guide
for information on how
these Delays and Run Times are used.
Description
Minimum
Default
Maximum
Cooling Stage Up
3 Min
3 Min
15 Min
Cooling Stage Down
1 Min
1 Min
15 Min
Cooling Min Run Time
5 Min
5 Min
15 Min
Cooling Min Off Time
3 Min
3 Min
15 Min
Heating Stage Up
3 Min
3 Min
15 Min
Heating Stage Down
1 Min
1 Min
15 Min
Heating Min Run Time
2 Min
5 Min
15 Min
Heating Min Off Time
1 Min
1 Min
15 Min
Con
fi
guration Screen #74 - Heat Pump Delays
- Aux Heat
VCCX Cnfg ID 101
Heat Pump Delays
Aux Heat..: 3 Min
[ 0 - 60 Minutes ]
If your VCC-X is con
fi
gured to operate as a Heat Pump, the Heat
Pump Auxiliary Heating Delay Setpoint can be con
fi
gured to provide
a time delay period before Auxiliary Heating Stages can be activated
once activation of the Compressor Heating Stages have been initi-
ated.
Default is 3 minutes.
Description
Minimum
Default
Maximum
Aux Heat Delay
0 Min
3 Min
60 Min
Con
fi
guration Screen #75 - Heat/Cool
Changeover Delay
VCC-X Cnfg ID #
Heat Cool Changeover
Delay: 5Min
[ 0 - 20 Minutes ]
Enter
the time in minutes for the time delay when the unit changes
over from a call to heating to a call to cooling and vice versa.
De-
fault is 5 minutes.
Con
fi
guration Screen #76 - Return Air Bypass
Control
VCC-X Cnfg ID #
Return Air Bypass
Control: NO
USE < or > TO CHANGE
Select
Yes if your HVAC unit requires Return Air Bypass Control for
Dehumidi
fi
cation Reheat.
Default is NO
. You must have t
he EM1
Expansion Module installed and con
fi
gured for this feature.
Con
fi
guration Screen #77 - Morning
Cool-Down Type
VCC-X Cnfg ID #
Morning Cool-Down
None
USE < or > TO CHANGE
You can choose between the following Morning Cool-Down options.
Default is None.
Available options are:
None
—There is no Cool-Down required.
Stand Alone
—
The VCC-X Controller is not
communicating to Orion VAV Box controls, but a
Cool-Down Relay can be con
fi
gured to signal boxes by
others to open.
Bcast Fixed to Boxes
—The VCC-X Controller is
communicating to Orion VAV Boxes and will broadcast
a command to the boxes to go to a Fixed Percentage
Position
or
Air
fl
ow while in Cool-Down. This
fi
xed
position is con
fi
gured in the VAV Box Controller.
Bcast Max to Boxes
—The VCC-X Controller is
communicating to Orion VAV Boxes and will broadcast
a command to the boxes to go to a Maximum Percentage
Position
or
Air
fl
ow while in Cool-Down. This maximum
position is con
fi
gured in the VAV Box Controller.