A-TS
45
https://a-ts.cn/en/
Setting
Functions
Setting
Functions
normally-close input
20
Disable close-loop
21
Disable PLC
22
Frequency setting method 1
23
Frequency setting method 2
24
Frequency setting method 3
25
Reserved
26
MS frequency 4
27
Terminal control mode is
forcibly enabled
28
Control mode 1
29
Control mode 2
30
Reserved
31
Reserved
32
Reserved
35
External stop command
36
Reserved
37
Inverter operation prohibiting
38
Reserved
40
Clear auxiliary reference
frequency
41
Reset PLC stop status
42
Clear counter record
43
Signal of triggering counter
44
Reserved
45
Reserved
The functions are explained as follows:
1: Foreward
2: Reverse
3~5: MS terminals ( 26 is MS frequency 4 )
If any three of P5.03~P5.05 are set at 3~5 or 26 respectively, Up to 16
segments of speed can be defined through the combination of the ON
and OFF state of the 4 terminals.
6~7: External fault signal ( normally-open/close input )
If the setting is 6~7, fault signal of external equipment can be input via the
terminal, which is convenient for the inverter to monitor the fault of
external equipment. Once the inverter receives the fault signal, it will
display “F.ED”. The fault signal has two input modes, i.e. normally-open
and normally-close.