Vb:manual torque boost Vmax:Max output volt.
Fz:cut-off freq.for torque boost fb:Basic output freq.
Output voltage
f
b
V
b
V
max
Output freq.
f
z
Figure 7-6 Torque boost ( shadow area: boost value )
P3.07 Torque boost:
0: AutoTorque boost;
Non-0: Mannual Torque boost
P3.08: Manual torque boost cut-off point
Cut-off frequency of relative frequency P0.06 percentage
P3.09~P3.10 Reserved
Reserved
P3.11 Compensation time
Range: 0.1
~
25.0s
【
0.1s
】
Compensation time constant:
To compensate filtering constant of frequency, more less this value more
faster the refreshing is.
P3.12 AVR function
Range: 0, 1, 2
【
0
】
0: Disabled
1: Always enabled
2: Disabled during decelerating
AVR: auto voltage adjustment. This function can keep constant output
voltage when the input voltage deviates from rated value. Therefore, the
function should be enabled all the time especially when the input voltage
is higher than the rated value.
If AVR is disabled during deceleration, the Dec time is shorter but the
current is higher, otherwise, the motor decelerates smoothly with lower
current, but the Dec time is longer.
P3.13 Reserved
Reserved