A-TS
42
https://a-ts.cn/en/
0
Output voltage(V)
Output frequency
Hz
Vmax
Fb
Vmax
:
Max output voltage (F0.10)
Fb
:
Basic operating frequency(F0.06)
0
Figure 7-4 V/F curve
You can define a curve by P3.01~P3.06, i.e. a polygonal line defined by 3
points V1, V2, V3 is Relative to the percentage of the maximum output
voltage.
Figure 7-5 User Defined V/F curve
When VFD worked in low frequency, setting torque boost
value reasonablely to counteractthe output voltage reduction, in order to
achieve sufficient output torque.
P3.07 Torque boost
Range: 0
~
30.0
%【
2.0
%】
P3.08 Manual torque boost cutoff point
Range: 0
~
50
%【
10.0
%】
Volt.
Freq.
Fb
100%
V1
V2
F1
F2
V3
F3
V1~V3: segment 1-3,voltage percentage
F1~F3: frequency segment 1-3
Fb: base frequency F0.06