F7 Group: Process Closloop PID Parameters ( Toal 34 )
Code
Name
Setting
Scope
Min
Unit
Defaulte
d Value
Address
Chang
e
P7.00
Close-loop
PID control
0: Non
Closeloop
PID control
run
1: Closeloop
PID control
run
1
0
700H
×
P7.01
Reference
input method
0:Digital
setting
( P7.05
value )
1: Reserved
2: Reserved
3: LED
keypad
potentiomet
er given
4: Reserved
1
0
701H
○
P7.02
Reserved
-
-
-
702H
*
P7.03
Input filter
0.01
~
50.00s
0.01
s
0.5s
703H
○
P7.04
Feedback
filter
0.01
~
50.00s
0.01
s
0.5s
704H
○
P7.05
Digital
referenceinp
ut
0.00
~
10.00V
0.01
0.00
705H
○
P7.06
Reserved
-
-
-
706H
*
P7.07
Reserved
-
-
-
707H
*
P7.08
Min input
0.0%
~
P7.10
0.1%
0.0
708H
○
P7.09
Feedback of
Min input
0.0
~
100.0%
0.1%
0.0%
709H
○
P7.10
Max input
P7.08
~
100.0%
0.1%
100.0%
70AH
○