Time
f
s
f
max
Freq.(HZ)
Figure 7-3 Relation of Start Freq. and Start Time
Note
:
The start frequency is not limited by lower limit of the frequency.
P2.03~P2.07 Reserved
Reserved
P2.08 Stop mode
Range: 0, 1, 2
【
0
】
0: Decelerate to stop
When the inverter receives Stop command, it will reduce output
frequency to zero and stop within preset deceleration time.
1: Coast to stop
When the inverter receives Stop command, it will stop outputting
frequency and stop gradually relying on load inertia.
2: Decele DC braking
When the inverter receives Stop command, it will reduce output
frequency within preset Dec time. When it arrives at the frequency
threshold of DC braking, the DC braking begins. Please refer to
P2.09~P2.12.
P2.09 Frequency threshold of DC
braking
Range: 0.00
~
60.00Hz
【
1.00Hz
】
P2.10 DC brake delay time
Range: 0.00
~
10.00s
【
0.00s
】
P2.11 DC brake current at stop
0.0~150.0
%【
120.0
%】
P2.12 DC brake time at stop
0.1
~
60.0s
【
0.5s
】
DC brake starting frequency: in stop process, when the frequency is
reached, began to DC brake.