that it has undergone in the current stage. After receiving Run command,
it will run at the preset frequency of the stage for the remaining time of the
stage
2: Start from the frequency where it stops:
When the inverter stops caused by Stop command or fault, it can record
both the time it has undergone in the current stage and the very
frequency when the inverter stops. It will pick up the recorded frequency
and run for the remaining time of the stage.
Hundred’s place of PD.00: Save PLC state after poweroff:
0: not save
The PLC state will not be saved when poweroff, and the inverter will start
from the first stage after powerup.
1: save
The PLC state, including the stage, frequency, run time will be saved
when poweroff and the inverter will start according to the setting of ten’s
place of PD.00 after powerup.
Thousand’s place: Selection of time unit:
0: Second
1: Minute
This unit is only valid for defining the PLC operating time. The unit of
Acc/Dec time in PLC operation is determined by P9.23.
PD.01 Stage 1 setting
Range: 000
~
323
【
000
】
PD.02 Stage 1 run time
Range: 0
~
6500s ( min )
【
20.0s
】
PD.03 Stage 2 setting
Range: 000
~
323
【
000
】
PD.04 Stage 2 run time
Range: 0
~
6500s ( min )
【
20.0s
】
PD.05 Stage 3 setting
Range: 000
~
323
【
000
】
PD.06 Stage 3 run time
Range: 0
~
6500s ( min )
【
20.0s
】
PD.07 Stage 4 setting
Range: 000
~
323
【
000
】