Function
Code
Register
address
Register
content
Checksum
Request
0x01
0x06
0x3202
0x0DAC
0x225F
Response
0x01
0x06
0x3202
0x0DAC
0x225F
Start the 1 # Inverter to run forward, set the speed as 50.00 HZ
( internally denote to be 5000 ) , command as follows:
addres
s
Functio
n Code
Registe
r
addres
s
Registe
r
number
Registe
r
content
bytes
Registe
r
content
Checksu
m
Request
0x01
0x10
0x3200
0x0002
0x04
0x01C7
,
0x1388
0x0399
Respons
e
0x01
0x10
0x3200
0x0002
none
none
0x4F70
Read 1 # Inverter output current, the Inverter responds output current of
30.0 A ( internally donote to be 300 ) :
address
Function
Code
Register
address
Register
number or
read number
of bytes
Register
content
Checksum
Request
0x01
0x03
0x3306
0x0001
none
0x6B4F
Response
0x01
0x03
none
0x02
0x012C
0xB809
11.5 The scaling rule of Inverter
A ) The calibration of frequency is 1:100
To make inverter running at 50 hz, the main setting should be 0 x1388
( 5000 ) .
B ) The calibration of time is 1:10
To make the acceleration time to be 30s, the function code setting
should be 0x012c ( 300 ) .
C ) The calibration of current is1:10
If the feedback current of inverter is 0x012c, the current of the inverter is
30A.