13.3 Troubleshooting table for displayed errors
Displayed errors
Code + description
Cause
Measure
Remark
S01 (blocking error)
Open circuit from
temperature sensor T
2
at the bottom of the
tank.
Sensor is not (correctly)
connected
Connect the sensor lead to JP3
See the electrical diagram (17 "Appendices").
Damaged cable and/or
defective sensor
Replace the cable and/or sensor.
To replace the necessary parts, you must contact your installation
engineer
S02 (blocking error)
Open circuit from
sensor 1 of
temperature sensor T
1
at the top of tank
(1)
.
Sensor is not (correctly)
connected
Connect the sensor lead to JP5
See the electrical diagram (17 "Appendices").
Damaged cable and/or
defective sensor
Damaged cable and/or defective sensor
To replace the necessary parts, you must contact your installation
engineer
S03 (blocking error)
Open circuit in sensor 2
of temperature sensor
T
1
at the top of the tank
(1)
.
Sensor is not (correctly)
connected
Connect the sensor lead to JP5
See the electrical diagram (17 "Appendices").
Damaged cable and/or
defective sensor
Replace the cable and/or sensor.
To replace the necessary parts, you must contact your installation
engineer
S04 (blocking error)
Open circuit from
dummy 1
Dummy is not
(correctly) connected
Connect the dummy sensor (dummy sensor 1 and 2) leads to JP4. See the electrical diagram (17 "Appendices").
Defective dummy
Replace the dummy sensor
To replace the necessary parts, you must contact your installation
engineer
S05 (blocking error)
Open circuit from
dummy 2
Dummy is not
(correctly) connected
Connect the dummy sensor (dummy sensor 1 and 2) leads to JP4. See the electrical diagram (17 "Appendices").
Defective dummy
Replace the dummy sensor
To replace the necessary parts, you must contact your installation
engineer
S06 (blocking error)
Open circuit from
temperature sensor S
3
at the top of the storage
tank
Sensor is not (correctly)
connected
Connect the sensor lead to J14 (port 1 and 3) of the solar controller See the electrical diagram (17 "Appendices").
Damaged cable and/or
defective sensor
Replace the cable and/or sensor.
To replace the necessary parts, you must contact your installation
engineer
Summary of Contents for SGS - 100
Page 7: ...4 Instruction manual SGS gis...
Page 11: ...Contents 8 Instruction manual SGS...
Page 23: ...Working principle of the water heater 20 Instruction manual SGS 2 gis...
Page 37: ...Installation types 34 Instruction manual SGS Installation 3...
Page 57: ...Conversion to a different gas category 54 Instruction manual SGS 4 is...
Page 65: ...Draining 62 Instruction manual SGS 6 gis...
Page 71: ...Status of the water heater 68 Instruction manual SGS 8 gis...
Page 75: ...Shutting down 72 Instruction manual SGS 10 gis...
Page 103: ...Service interval 100 Instruction manual SGS 14 is...
Page 112: ...Instruction manual SGS 109 is...
Page 119: ...Instruction manual SGS 116...