Code and description
Cause
Measure
F03
(lock out error)
Air proving switch error
Switch is not closed when
fan is running during pre-
purge.
Hoses are damaged.
-
Make sure that the hoses, between
the air proving switch and fan and the
air proving switch and gas control
valve are not damaged and reset the
controller.
-
If necessary replace the hose(s)
-
When the hose(s) are replaced and
reconnected, reset the controller.
Wiring is damaged.
-
Make sure that the wiring, between
the air proving switch and the control,
is connected and not damaged.
-
If necessary, replace the wires or
reconnect the wires.
-
When wires are replaced or
reconnected, reset the controller.
Leakage of air between venturi and
flexible air connector.
-
Make sure that the flexible air
connector is not damaged. If
necessary, replace the flexible air
connector.
-
Make sure that the hose is properly
connected to the venturi. If necessary,
tighten the clamp.
Non return valve, between fan and
burner, is stuck.
Make sure that the non return valve can
move freely. If necessary replace the non
return valve.
Not enough pressure differential across
the air proving switch, due to:
-
venting system
-
malfunctioning condensation
discharge
-
dirty burner
-
blocked heat exchanger
Check, after each fix, if the error reappears.
If the error reappears continue in finding
the cause.
-
Measure the pressure differential
across the air proving switch, refer to
Air pressure differential (see 8.9.2).
Venting system (see 8.7):
-
Make sure if the venting system is
compliant.
-
Make sure that the venting system has
no blockages.
-
Make sure if the air inlet screen has no
blockages.
Condensation discharge:
-
Make sure the condensate drain has
no blockages.
-
Make sure that the condensate drain is
connected to the waste water
discharge by an open connection.
Burner:
-
Make sure that the the burner is clean
(see 11.4.1).
-
Measure the pressure differential
across the air proving switch again. If
the pressure differential is insufficient,
clean the heat exchanger.
-
Make sure that the air proving switch
is closing, by using a multimeter.
76
Installation, Maintenance and Service part
Summary of Contents for Innovo IR 12-160
Page 6: ...6 ...
Page 13: ...User part 0312266_INNOVO_UKUK_V5 1 2022 07 12 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 27: ...Installation Maintenance and Service part 0312266_INNOVO_UKUK_V5 1 2022 07 12 27 ...
Page 28: ...28 User part ...
Page 36: ...36 Installation Maintenance and Service part ...
Page 56: ...56 Installation Maintenance and Service part ...
Page 58: ...58 Installation Maintenance and Service part ...
Page 70: ...70 Installation Maintenance and Service part ...
Page 83: ...0312266_INNOVO_UKUK_V5 1 2022 07 12 83 ...
Page 87: ...13 4 Electrical wiring diagram 0312266_INNOVO_UKUK_V5 1 2022 07 12 87 ...
Page 89: ...13 5 Declaration of conformity 0312266_INNOVO_UKUK_V5 1 2022 07 12 89 ...
Page 90: ......
Page 91: ......
Page 94: ...92 Installation Maintenance and Service part ...