8.9
Commissioning
To commission the water heater:
1.
Fill the water heater (see 8.9.1)
2.
Check the air pressure differential (see 8.9.2)
3.
Check the gas supply pressure (see 8.9.3)
4.
value (see 8.9.4)
5.
Turn on the water heater (see 8.9.5)
8.9.1
Filling
Refer to the installation diagram (see 8.3) when you fill the water heater:
1.
Open the stop valve (11) in the hot water supply pipe.
2.
If applicable, open the stop valves (4) of the circulation pipe (C).
3.
Make sure that the drain valve (9) is closed.
4.
Open the nearest hot water draw-off point (14).
5.
Open the stop valve (4) of the cold water supply pipe (A). Cold water flows into the
water heater.
6.
Fill the water heater until a full water jet flows from the nearest draw-off point. The
water heater is completely full.
7.
Open all draw-off points to bleed the entire installation of air.
The water heater is now under water supply pressure.
8.
Make sure that no water comes out of the expansion valve (15) or the T&P valve (3).
If water comes out:
-
Examine if the water supply pressure is greater than the specified value in the
Technical details. If necessary, install a pressure reducing valve (1).
-
Examine if the expansion valve in the protected cold supply set-up is installed
correctly and is not defect. If necessary, replace the expansion valve.
8.9.2
Air pressure differential
Check the air pressure differential across the air pressure switch:
1.
Disconnect hose H of the air proving switch and connect this side of the hose to the
+ of the pressure gauge.
2.
Disconnect hose L of the air pressure switch and connect this side of the hose to the
- of the pressure gauge.
3.
Turn the water heater on and set the water heater in OFF mode, refer to Turn on the
water heater (see 4.2).
Note
Make sure that the water heater is not in ON mode or in External ON mode.
4.
Set parameter
201
to
FAn
, refer to Settings (see 10).
5.
Read the pressure value from the meter.
6.
Compare the measured value to the value from the table.
Note
When the air pressure differential is not correct, refer to Displayed errors (see
12.1.2), error
F03
.
7.
Set parameter
201
to
dIS
, refer to Settings (see 10).
8.
Press [RESET].
The water heater goes into OFF mode.
9.
Set the control switch on the side of the water heater to 0 to turn off the water
heater.
n
n
52
Installation, Maintenance and Service part
Summary of Contents for Innovo IR 12-160
Page 6: ...6 ...
Page 13: ...User part 0312266_INNOVO_UKUK_V5 1 2022 07 12 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 27: ...Installation Maintenance and Service part 0312266_INNOVO_UKUK_V5 1 2022 07 12 27 ...
Page 28: ...28 User part ...
Page 36: ...36 Installation Maintenance and Service part ...
Page 56: ...56 Installation Maintenance and Service part ...
Page 58: ...58 Installation Maintenance and Service part ...
Page 70: ...70 Installation Maintenance and Service part ...
Page 83: ...0312266_INNOVO_UKUK_V5 1 2022 07 12 83 ...
Page 87: ...13 4 Electrical wiring diagram 0312266_INNOVO_UKUK_V5 1 2022 07 12 87 ...
Page 89: ...13 5 Declaration of conformity 0312266_INNOVO_UKUK_V5 1 2022 07 12 89 ...
Page 90: ......
Page 91: ......
Page 94: ...92 Installation Maintenance and Service part ...