Indication
Cause
Measure
CO
2
value (at full load)
is not correct
The unit is not set for the correct gas
type
-
Make sure that the gas type
corresponds with the information on
the rating plate
-
Make sure if the venturi restrictor has
the correct diameter, refer to Gas
details.
Contaminated venturi
Remove any contamination from the venturi
inlet.
Leakage between venturi and flexible
venturi connector
-
Make sure that the flexible venturi
connector is not damaged.
If necessary replace the flexible
venturi connector
-
Make sure that the flexible venturi
connector is correctly connected.
If necessary, tighten the clamp.
Recirculation of flue gases
-
Make sure that the CO
2
-value
measured in the flue gas outlet is
correct, refer to CO
value (see 8.9.4).
-
Make sure that the CO
2
value
measured in the air inlet is below
0.5 vol%.
-
If necessary, reconnect the venting
system and change the necessary
seals.
0312266_INNOVO_UKUK_
V5.1, 2022-07-12
73
Summary of Contents for Innovo IR 12-160
Page 6: ...6 ...
Page 13: ...User part 0312266_INNOVO_UKUK_V5 1 2022 07 12 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 27: ...Installation Maintenance and Service part 0312266_INNOVO_UKUK_V5 1 2022 07 12 27 ...
Page 28: ...28 User part ...
Page 36: ...36 Installation Maintenance and Service part ...
Page 56: ...56 Installation Maintenance and Service part ...
Page 58: ...58 Installation Maintenance and Service part ...
Page 70: ...70 Installation Maintenance and Service part ...
Page 83: ...0312266_INNOVO_UKUK_V5 1 2022 07 12 83 ...
Page 87: ...13 4 Electrical wiring diagram 0312266_INNOVO_UKUK_V5 1 2022 07 12 87 ...
Page 89: ...13 5 Declaration of conformity 0312266_INNOVO_UKUK_V5 1 2022 07 12 89 ...
Page 90: ......
Page 91: ......
Page 94: ...92 Installation Maintenance and Service part ...