Refer to the table for the correct pipe dimensions of the C13 or a C33 parallel venting
systems.
Description
Unit
BFC 2
8
- 60
(1)
BFC 80 - 120
(2)
Default
Diameter flue discharge/
air inlet
mm
2x100
2x130
Maximum length air inlet
m
55
65
Maximum length flue gas
outlet
m
55
65
L
equivalent
45°-bend
m
1,2
1,4
L
equivalent
90°-bend
m
4,6
2,4
Diameter enlargement
Diameter flue discharge/
air inlet
mm
2x130
2x150
Maximum length air inlet
m
100
100
Maximum length flue gas
outlet
m
100
100
L
equivalent
45°-bend
m
1,4
1,6
L
equivalent
90°-bend
m
2,4
2,6
1 - When the maximum total length for the default diameter of 100 mm is insufficient,
diameter 130 mm should be used. Any diameter enlargement must be carried out on both
air inlet and flue gas outlet.
2 - When the maximum total length for the default diameter of 130 mm is insufficient,
diameter 150 mm should be used. Any diameter enlargement must be carried out on both
air inlet and flue gas outlet.
Caution
Always make sure the installation is in compliance with the requirements stated in this
table.
Caution
Use a run-off of 50 mm per meter towards the water heater.
Calculate the maximum length of the air inlet and the flue gas outlet seperately:
Sum the lengths of the different pipe sections without bends. Ignore the length of
the adaptor box.
Sum the lengths of the bends. Ignore the bend in the adapter box:
Sum L
equivalent
for each 45° bend.
Sum L
equivalent
for each 90° bend.
Sum the lengths of the pipe sections and the lengths of the bends to calculate the
overall length of the air inlet and the flue gas outlet.
Adjust the length of the air inlet and/or the flue gas outlet when the overall length
exceeds the maximum length as stated in the table.
c
1.
2.
-
-
3.
4.
0311704_BFC_28-120_III_
ENEN_V2.4, 2022-10-17
63
Summary of Contents for BFC Cyclone 120
Page 6: ...6 ...
Page 13: ...User part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 41: ...Installation Maintenance and Service part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 41 ...
Page 42: ...42 User part ...
Page 46: ...46 Installation Maintenance and Service part ...
Page 52: ...52 Installation Maintenance and Service part ...
Page 59: ...Fig Venting systems 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 59 ...
Page 76: ...76 Installation Maintenance and Service part ...
Page 78: ...78 Installation Maintenance and Service part ...
Page 84: ...84 Installation Maintenance and Service part ...
Page 102: ...Fig Dimensions BFC 28 30 50 60 102 Installation Maintenance and Service part ...
Page 104: ...Fig Dimensions BFC 80 100 120 104 Installation Maintenance and Service part ...
Page 112: ...12 7 Declaration of conformity 112 Installation Maintenance and Service part ...
Page 113: ......
Page 114: ......
Page 118: ...116 Installation Maintenance and Service part ...