The electrical section is now visible.
Remove the black caps from the measurement point of the pressure switch.
Connect the + of the pressure gauge to the H of the measurement point of the
pressure switch.
Connect the - of the pressure gauge to the L of the measurement point of the
pressure switch.
Zero the pressure gauge.
Start the appliance (see section 4.1).
The appliance will now run the heating cycle (see section 4.1.1).
Read the pressure from the meter at the moment when the appliance switches from
PRE PURGE to PRESSURE SWITCH. At this point, the appliance's display will show:
Check whether the measured value matches the value from the table (see section
12.1).
Note
If the message PRESSURE SWITCH does not appear, there is a fault. This must be
resolved first by a qualified service engineer.
Shut off the gas supply.
Disconnect the pressure gauge.
Put the two black caps back on the pressure switch.
Replace the covers.
7.8.6
Turn on the water heater
Refer to the procedure in the user part to Turn on the water heater (see section 4.1).
7.9
Decommisioning
To decommission the water heater:
Turn off the water heater (see section 7.9.1)
Drain the water heater
7.9.1
Turn off the water heater
Refer to the procedure in the user part to Turn off the water heater (see section 4.2) and
isolate the water heater from the mains power supply.
7.9.2
Draining
7.9.2.1
Draining unvented installations
Some service activities require the water heater to be drained. The procedure is as
follows:
Activate the MENU with [
].
Position the cursor in front of OFF.
Confirm OFF with [ENTER].
Wait until the fan has stopped. The icon is then dimmed.
Caution
Failure to wait until the fan stops can cause damage to the water heater.
3.
4.
5.
6.
7.
8.
9.
10.
11.
n
12.
13.
14.
15.
1.
2.
1.
2.
3.
4.
c
74
Installation, Maintenance and Service part
Summary of Contents for BFC Cyclone 120
Page 6: ...6 ...
Page 13: ...User part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 41: ...Installation Maintenance and Service part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 41 ...
Page 42: ...42 User part ...
Page 46: ...46 Installation Maintenance and Service part ...
Page 52: ...52 Installation Maintenance and Service part ...
Page 59: ...Fig Venting systems 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 59 ...
Page 76: ...76 Installation Maintenance and Service part ...
Page 78: ...78 Installation Maintenance and Service part ...
Page 84: ...84 Installation Maintenance and Service part ...
Page 102: ...Fig Dimensions BFC 28 30 50 60 102 Installation Maintenance and Service part ...
Page 104: ...Fig Dimensions BFC 80 100 120 104 Installation Maintenance and Service part ...
Page 112: ...12 7 Declaration of conformity 112 Installation Maintenance and Service part ...
Page 113: ......
Page 114: ......
Page 118: ...116 Installation Maintenance and Service part ...