Code and description
Cause
Measure
F11 (blocking error)
Flame detection with
closed gas control valve.
Defective gas control valves
See F07.
F19 (blocking error)
Power supply voltage is
too low.
There is not enough supply voltage.
Check that there is power to the
controller
The measured voltage must be 230 VAC
(-15%, +10%)
1.
2.
C02 (lock out error)
Error message from the
controller.
Incorrect reference voltage from the AD
converter.
Reset controller.
Check that the frequency of the power
supply is compliant (see section 12.1). If
not, contact your installation engineer
If the frequency is correct but the error
persists, replace the controller.
1.
2.
3.
Internal error message
from the controller.
EEPROM read error
50 Hz error
Internal communication error
•
•
•
Internal error message
from the controller.
Gas valve relay error
Safety relay error
Ignition relay error
RAM error
EEPROM error
EEPROM contents do not match the
software version
Processor software error
•
•
•
•
•
•
•
C03 (blocking error)
Reset error
Too many resets in too short a period
Wait for the error to disappear (maximum 1
hour). If the error does not disappear,
replace the water heater controller.
C04 (blocking error)
Appliance selection error
Incorrect water heater selection /
Incorrect selection resistor
Check whether the correct water heater
is selected (see section 12.1).
If the correct water heater is selected, fit
the correct selection resistor.
If incorrect water heater selected, select
the correct one.
1.
2.
3.
E01 (blocking error)
The temperature
protection at the top of
the tank has been
activated.
The temperature of the water at the top
of the tank is > 88 ºC.
None. This is a temporary message that
may appear from time to time, but will
disappear automatically.
E03 (lock-out error)
Error in temperature
sensor T
1
at the top of the
tank.
The two temperature sensors in the tank
detect a difference of > 10°C over a
period of at least 60 seconds.
Check sensor position and wiring.
Reset the controller if necessary. Replace
the sensor if the error persists.
1.
2.
E04 (lock-out error)
Defect in the dummy
sensor
(2)
.
The two temperature sensors detect a
difference of >10 ºC over a period of at
least 60 seconds.
Check the wiring of the dummy 1 and
dummy 2.
Reset the controller if necessary. Replace
the dummy sensor if the error persists.
1.
2.
0311704_BFC_28-120_III_
ENEN_V2.4, 2022-10-17
95
Summary of Contents for BFC Cyclone 120
Page 6: ...6 ...
Page 13: ...User part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 41: ...Installation Maintenance and Service part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 41 ...
Page 42: ...42 User part ...
Page 46: ...46 Installation Maintenance and Service part ...
Page 52: ...52 Installation Maintenance and Service part ...
Page 59: ...Fig Venting systems 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 59 ...
Page 76: ...76 Installation Maintenance and Service part ...
Page 78: ...78 Installation Maintenance and Service part ...
Page 84: ...84 Installation Maintenance and Service part ...
Page 102: ...Fig Dimensions BFC 28 30 50 60 102 Installation Maintenance and Service part ...
Page 104: ...Fig Dimensions BFC 80 100 120 104 Installation Maintenance and Service part ...
Page 112: ...12 7 Declaration of conformity 112 Installation Maintenance and Service part ...
Page 113: ......
Page 114: ......
Page 118: ...116 Installation Maintenance and Service part ...