7.6.3
C43/C53/C63 systems
The length of the air inlet and flue gas outlet is the same for C43, C53 and C63 systems as
for C13 and C33 systems:
Refer to C13/C33 concentric systems for the maximum pipe lengths of concentric
systems.
Refer to C13/C33 parallel systems for the maximum pipe lengths of parallel systems
and non-concentric systems.
Note
Only use a C43 venting system when the common duct is a natural draught chimney. The
common duct is part of the building, not a part of the system.
Note
In a C53 venting system the flue gas terminal must be CE approved and must comply to
the EN 1856-1 requirements.
Note
Connect a C63 venting system to a separately approved and marketed system for the
supply of combustion air and discharge of flue gasses.
The flue gas terminal must comply to the EN 1856-1 requirements. The maximum
allowable recirculation rate is 10% under wind conditions.
Contact A.O. Smith for more information and/or part numbers of the C43, C53 and C63
venting systems.
Concentric systems
Refer to the table for the correct pipe dimensions of the C43, C53 and C63 concentric
systems.
Description
BFC 28 - 60
BFC 80 - 120
Manufacture venting material Muelink & Grol
Muelink & Grol
Construction
Concentric
Concentric
Material flue gas outlet
Thick walled aluminum Thick walled aluminum
Material air inlet
Thin walled galvanized
steel
Thin walled galvanized
steel
Diameter flue gas outlet
100 mm
130 mm
Diameter air inlet
150 mm
200 mm
Refer to C13/C33 concentric systems for the A.O. Smith part numbers. The same parts can
be used for the C43, C53 and C63 concentric systems.
Parallel and non-concentric systems
Refer to the table for the correct pipe dimensions of the C43, C53 and C63 parallel
systems.
Description
BFC 28 - 60
BFC 80 - 120
Manufacture venting material Muelink & Grol
Muelink & Grol
Construction
Parallel
Parallel
Material flue gas outlet
Thick walled aluminum Thick walled aluminum
Material air inlet
Diameter flue gas outlet
100
+0,6
/
-0,6
mm
130
+0,6
/
-0,6
mm
Diameter air inlet
Refer to C13/C33 parallel systems for the A.O. Smith part numbers. The same parts can
be used for the C43, C53 and C63 parallel systems.
Use the "adapter box concentric to parallel - water heater side" (part number 0312209) for
C63 parallel systems.
•
•
n
64
Installation, Maintenance and Service part
Summary of Contents for BFC Cyclone 120
Page 6: ...6 ...
Page 13: ...User part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 41: ...Installation Maintenance and Service part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 41 ...
Page 42: ...42 User part ...
Page 46: ...46 Installation Maintenance and Service part ...
Page 52: ...52 Installation Maintenance and Service part ...
Page 59: ...Fig Venting systems 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 59 ...
Page 76: ...76 Installation Maintenance and Service part ...
Page 78: ...78 Installation Maintenance and Service part ...
Page 84: ...84 Installation Maintenance and Service part ...
Page 102: ...Fig Dimensions BFC 28 30 50 60 102 Installation Maintenance and Service part ...
Page 104: ...Fig Dimensions BFC 80 100 120 104 Installation Maintenance and Service part ...
Page 112: ...12 7 Declaration of conformity 112 Installation Maintenance and Service part ...
Page 113: ......
Page 114: ......
Page 118: ...116 Installation Maintenance and Service part ...