Indication
Cause
Measure
Insufficient or no hot
water
The water heater is off.
Turn on the water heater (see section 4.1).
There is no supply voltage.
Make sure that:
the control switch is set to I.
the isolator is in ON position.
there is power on the isolator.
there is power to the electrical connector
block.
The measured voltage must be
230 V
AC
(-15%, +10%).
•
•
•
•
The hot water supply is used up.
Reduce the hot water consumption. Wait
until the water heater heats up.
The controller is in the OFF mode.
Set the controller in the ON mode.
The temperature (T
set
) is set too low.
Set the temperature (T
set
) to a higher value.
CO
2
value (at full load)
is not correct
The unit is not set for the correct gas
type
Make sure that the gas type corresponds
with the information on the rating plate
Make sure if the venturi restrictor has the
correct diameter, refer to Gas details.
•
•
Contaminated venturi
Remove any contamination from the venturi
inlet.
Leakage between venturi and flexible
venturi connector
Make sure that the flexible venturi
connector is not damaged.
If necessary replace the flexible venturi
connector
Make sure that the flexible venturi
connector is correctly connected.
If necessary, tighten the clamp.
•
•
Recirculation of flue gases
Make sure that the CO
2
-value measured
in the flue gas outlet is correct, refer to
CO
2
value.
Make sure that the CO
2
value measured
in the air inlet is below 0.5 vol%.
If necessary, reconnect the venting
system and change the necessary seals.
•
•
•
11.1.2
Displayed errors
Note
For the coding of the connections, refer to the Electrical wiring diagram.
Note
Contact your service and maintenance engineer if the error persists.
Code and description
Cause
Measure
S01 (blocking error)
Open circuit from
temperature sensor T
2
at
the bottom of the tank.
Sensor is not (correctly) connected
Connect the sensor lead to JP3
Damaged cable and/or defective sensor
Replace the cable and/or sensor
n
0311704_BFC_28-120_III_
ENEN_V2.4, 2022-10-17
91
Summary of Contents for BFC Cyclone 120
Page 6: ...6 ...
Page 13: ...User part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 41: ...Installation Maintenance and Service part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 41 ...
Page 42: ...42 User part ...
Page 46: ...46 Installation Maintenance and Service part ...
Page 52: ...52 Installation Maintenance and Service part ...
Page 59: ...Fig Venting systems 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 59 ...
Page 76: ...76 Installation Maintenance and Service part ...
Page 78: ...78 Installation Maintenance and Service part ...
Page 84: ...84 Installation Maintenance and Service part ...
Page 102: ...Fig Dimensions BFC 28 30 50 60 102 Installation Maintenance and Service part ...
Page 104: ...Fig Dimensions BFC 80 100 120 104 Installation Maintenance and Service part ...
Page 112: ...12 7 Declaration of conformity 112 Installation Maintenance and Service part ...
Page 113: ......
Page 114: ......
Page 118: ...116 Installation Maintenance and Service part ...