ZXCBTS (V5.4) CDMA Micro Base Transceiver Station & Remote Station Installation Manual
6-2
Feeder cable grounding kit
T ower platform
U
Feeder cable
Grounding cable (35mm
2
)
Mi
cr
o-
B
T
S
D
C
p
ow
er
ra
ck
O
th
er
d
ev
ices
Outdoor
grounding
busbar
Indoor
grounding
busbar
PGNDs of all devices in the
equipment room (including the
cabling rack) are connected to
the indoor grounding busbar
Grounding cable (50mm
2
)
Fig. 6.1-1 Schematic Diagram of Grounding Connections
6.2 Installing Grounding System
6.2.1 Installing Outdoor Grounding Copper Busbar
The outdoor grounding copper busbar functions in lightning protection. It is usually
installed on the wall outside the equipment room, and the best position is right under
the feeder cable window or on the rain-proof wall of the feeder cable well on the top of
a building.