Autodiagnostics
The.table.List.of.errors.–.same.as.for.electronics.DMS2.ED.
(page 13)
Memory of number of induced errors
–. For.all.detected.errors,.DMS2.uses.the.counter.of.occurrence.of.these.errors.during.operation.of.the.system.
–. .Values.of.the.counters.are.stored.to.the.EEPROM.memory.and.are.preserved.even.in.case.of.the.power.supply.
fall-out.
–. Reading.and.clearing.of.the.counters.is.possible.by.means.of.the.program.for.PC.
Memory of recently induced errors
–. DMS2.stores.3.recently.induced.errors.to.the.memory.EEPROM.
–. DMS2.provides.for.displaying.the.errors.by.means.of.the.PC.program.or.the.switches.of.the.local/.remote.control.
–. .The.display.in.MENU.22.INFORMATION.shows.ERROR.1,.ERROR.2,.ERROR.3..ERROR.1.is.the.latest.error.
Setting parameters by means of push-buttons of local control
Signalization.of.operation.regimes.by.means.of.diodes.LED.on.the.position.sensor.board:
Red
Green
State
.
-.
-.
System.without.feeding.
.
-.
lit.on.
Everything.OK.–.working.regime.
(remote, local, or switched off control)
.
blinking..
lit.on..
Error.or.warning.–.working.regime.
(remote, local, or switched off control)
.
lit.on..
lit.on..
Setting.parameters.by.means.of.push-buttons.or.PC.
Signalization.of.operation.regimes.by.means.of.the.display:
The display shows the actuator position in %, the state of local control and/or reaching of torque. In case of an error,
blinking of this state alternates with number of actual error. In case of more errors, these errors repeat cyclically.
Overview of MENU
.
Name
Parameter value
Meaning
.
1. JAZ/LANGUAGE.
.
CESKY..
Menu.LANGUAGE.
. . .
ENGLISH.
. 2. POLOHA.O,.Z
.
POL.OTEVR..
End-limit.position.Open.or.Closed
.
. . .
POL.ZAVRENO.
. 3. KALIBRACE.
SPUSTIT.
Starting.of.autocalibration.
. . .
MOMENT.
. 4. KONCOVA.POL..
.
POL.O..
Tripping.in.end-limit.positions
. . .
POL.Z.
. . .
P.O+Z.
. 5. MOMENT.PR..O..
50.–.100.%.
.
.Working.torque.Open.
(selection 50 – 69 % depends on parameter Torque min.)
.
. 6. MOMENT.PR..Z.
50.–.100.%
.
.Working.torque.Closed.
(selection 50 – 69 % depends on parameter Torque min.)
.
. 7. CAS.BLOK.MOM.
0.–.20.s..
Time.of.torque.blocking.
. 8.. POLOHA.BL..O..
0.–.50.%.
Position.of.torque.blocking.Open.
. 9.. POLOHA.BL..Z..
0.–.50.%.
Position.of.torque.blocking.Closed.
.10.. CPT
.
4.–.20.mA.
Characteristics.of.current.transducer.
. . .
20.–.4.mA.
. . .
4.–.20.mA..
.11.. RIDICI.SIGN.
.
20.–.4.mA..
Analog.control.signal
. . .
0.–.20.mA.
. . .
20.–.0.mA.
.12. NECITLIVOST.
1.–.10.%..
Range.of.insensitivity.
.. . .
OTEVIRAT..
.13.. SAFE
.
ZAVIRAT..
Response.to.signal.Safe.and.loss.of.control.signal
. . .
ZASTAVIT.
. . .
POLOHA.