10
keeping.it.depressed,.the.actuator.can.be.further.shifted..After.required.position.is.reached,.it.is.stored.to.
memory.by.pressing.push-button.C.or.O.
Parameters that can be changed by user are set by manufacturer as follows:
1... Tripping.torques:.
.100%.or.required.value.
(it is not recommended to change the value
without consulting the supplier of the valve, etc.).
2.. Relay.3.and.relay.4:..
signalization.SZ.1.%.and.SO.99.%.of.stroke
3.. Time.of.blocking:.
0.s
4... Position.of.blocking:.
.5.%.of.stroke.from.end-limit.positions.
(it is not recommend to change
the value by more than 10 %)
5... Characteristics.of.position.transducer:..
closed.4.mA,.open.20.mA.
6... Relay.READY:..
.w.not.remote
In.version.CONTROL:.
1.. Setting.of.control.signal:..
closed.4.mA,.open.20.mA
2... Insensitivity.of.actuator.in.regulation:..
1.%.
(it is not recommended to set insensitivity higher than 3 %)
3... Response.in.case.of.loss.of.control.signal:..
stop.
4... Way.of.switch.off.in.end-limit.positions:..
.PO.+.PZ.
Overview of MENU
BROWSING.THROUGH.MENU
–. .The.setting.regime.is.entered.by.pressing.and.keeping.depressed.push-button.
MENU.for.at.least.2.s;.LED1.is.then.lit.on.
–.. .Shortly.press.
MENU.to.select.the.basic.MENU.–.menu.M1.to.M8.
(LED1 signalizes the menu number);
by.short.
pressing.of.P,.O,.C.they.are.entered
(LED2 signalizes particular parameter).
–. .Shortly.press.P.to.select.required.value.of.the.parameter..In.case.the.parameter.can.be.set.to.several.values,.they.
are.changed.by.short.pressing.of.P.
(number of blinking of LED2 indicates its value).
.Keep.pressing.of.P.to.record.
the.chosen.parameter;.the.record.is.confirmed.by.lighting.on.of.LED2..
–.. .Shortly.press.
MENU.to.gradually.set.the.required.menu.and.parameters.
–.. .After.setting.all.required.parameters,.exit.the.setting.menu.by.pressing.and.keeping.depressed.push-button.
MENU.for.at.least.2.s..The.setting.menu.will.also.be.left.in.case.that.no.push-button.is.pressed.within.1.minute.
MENU 1 – Setting of tripping torques
–. After.entering.the.menu.by.means.of.push-button.C.or.O,.select.required.torque.
–. .Shortly.press.P.to.select.the.set.value.of.the.parameter.50.–.100.%.
(5 – 10 blinking of LED2)
.and.keep.pressing.
push-button.P.to.store.the.parameter.to.memory.
MENU 2 – Setting function of signalling relays
–. Basic.setting.of.the.signalling.relays.is.SZ.1.%.and.SO.99.%.of.stroke.
–. ..In.case.different.setting.is.required,.it.can.be.changed.after.shifting.the.actuator.to.required.position.by.means.of.
push-button.C.or.O.
–. Using.push-button.P,.perform.basic.setting.SZ.1.%.and.SO.99.%.of.stroke.
MENU 3 – Setting of blocking of torque in end-limit positions
–. ..Shortly.press.P.to.select.the.set.value.of.blocking.time.0.–.20.s.
(0 – 20 blinking of LED2)
.and.keep.pressing.push-
-button.P.to.store.the.parameter.to.memory.
–. Keep.pressing.push-button.C.to.store.actual.position.for.blocking.torque.on.the.side.Closed.to.memory.
–. Keep.pressing.push-button.O.to.store.actual.position.for.blocking.torque.on.the.side.Open.to.memory.
MENU 4 – Setting transducer characteristics
–. ..Shortly.press.P.to.select.the.value.4.–.20.mA.–.1x.blinking.of.LED2.or.20.–.4.mA.–.2x.blinking.of.LED2,.and.keep.
pressing.push-button.P.to.store.the.parameter.to.memory..
Other menus only serve for board setting in version Control
MENU 5 – Setting control signal in 3P regulation
–. .Shortly.press.P.to.select.value. ....4.–.20.mA..
-.1x.blinking.of.LED2,.
.
.
or.20.–.4.mA..
-.2x.blinking.of.LED2,.
.
.
or.0.–.20.mA..
-.3x.blinking.of.LED2,.
.
.
or.20.–.0.mA..
-.4x.blinking.of.LED2.
.
and.keep.pressing.push-button.P.to.store.the.parameter.to.memory.